EasyManua.ls Logo

Panasonic U-100PE1E5A - Single Split (R410 A) - 3-Phase Europe; Single Split (R32) - Europe;Oceania

Panasonic U-100PE1E5A
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86
Single Split Outdoor Unit (R410A)
Europe
Model Name
U-71PE1E8A U-100PE1E8A U-125PE1E8A U-140PE1E8A
Power source 380 - 400 - 415 V 3N
50 Hz
Oceania
Model Name
U-100PE1R8A U-125PE1R8A U-140PE1R8A
Power source 400 - 415 V 3N
50 Hz
Cooling capacity
kW
7.1 10.0 12.5 14.0
BTU/h
24,200 34,100 42,700 47,800
Heating capacity
kW
8.0 11.2 14.0 16.0
BTU/h
27,300 38,200 47,800 54,600
Sound Pressure level
(Cooling / Heating)
dB(A)
48 / 50 52 / 52 53 / 53 54 / 55
Sound Power level
(Cooling / Heating)
dB(A)
65 / 67 69 / 69 70 / 70 71 / 71
Unit Dimensions
(H×W×D)
mm
996×940×340 1,416×940×340 1,416×940×340 1,416×940×340
Net weight
kg
71 98 98 98
Operation condition temperature range
•Coolingmode:-15°C~46°CDB•Heatingmode:-20°C~18°CWB/-20°C~24°CDB
Europe
Model Name
U-60PEY2E5 U-71PEY2E5 U-100PEY1E5 U-125PEY1E5
Power source 220 - 230 - 240 V
50 Hz
Cooling capacity
kW
6.0 7.1 10.0 12.5
BTU/h
20,500 24,200 34,100 42,700
Heating capacity
kW
6.0 7.1 10.0 12.5
BTU/h
20,500 24,200 34,100 42,700
Sound Pressure level
(Cooling / Heating)
dB(A)
46 / 48 49 / 49 54 / 54 56 / 56
Sound Power level
(Cooling / Heating)
dB(A)
65 / 68 69 / 69 70 / 70 73 / 73
Unit Dimensions
(H×W×D)
mm
619×799×299 619×799×299
996×940×340 996×940×340
Net weight
kg
40 40 73 85
Operation condition temperature range
•Coolingmode:-10°C~43°CDB•Heatingmode:-15°C~18°CWB/-15°C~24°CDB
Europe
Model Name
U-100PEY1E8 U-125PEY1E8 U-140PEY1E8
Power source 380 - 400 - 415 V 3N
50 Hz
Cooling capacity
kW
10.0 12.5 14.0
BTU/h
34,100 42,700 47,800
Heating capacity
kW
10.0 12.5 14.0
BTU/h
34,100 42,700 47,800
Sound Pressure level
(Cooling / Heating)
dB(A)
54 / 54 56 / 56 54 / 53
Sound Power level
(Cooling / Heating)
dB(A)
70 / 70 73 / 73 71 / 70
Unit Dimensions
(H×W×D)
mm
996×940×340 996×940×340 1,416×940×340
Net weight
kg
73 85 98
Operation condition temperature range
•Coolingmode:-10°C~43°CDB•Heatingmode:-15°C~18°CWB/-15°C~24°CDB
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.