85
Outdoor unit
Single Split Outdoor Unit (R410A)
Europe
Model Name
U-36PE2E5A U-50PE2E5A U-60PE2E5A
Power source 220 - 230 - 240 V
50 Hz
Cooling capacity
kW
3.6 5.0 6.0
BTU/h
12,300 17,100 20,500
Heating capacity
kW
4.0 5.6 7.0
BTU/h
13,600 19,100 23,900
Sound Pressure level
(Cooling / Heating)
dB(A)
45 / 46 46 / 48 46 / 49
Sound Power level
(Cooling / Heating)
dB(A)
64 / 66 65 / 68 65 / 69
Unit Dimensions
(H×W×D)
mm
619×799×299 619×799×299 619×799×299
Net weight
kg
39 39 40
Operation condition temperature range
•Coolingmode:-15°C~46°CDB•Heatingmode:-20°C~18°CWB/-20°C~24°CDB
Europe
Model Name
U-71PE1E5A U-100PE1E5A U-125PE1E5A U-140PE1E5A
Power source 220 - 230 - 240 V
50 Hz
Oceania
Model Name
U-60PE1R5A U-71PE1R5A U-100PE1R5A U-125PE1R5A U-140PE1R5A
Power source 230 - 240 V
50 Hz
Cooling capacity
kW
6.0 7.1 10.0 12.5 14.0
BTU/h
20,500 24,200 34,100 42,700 47,800
Heating capacity
kW
7.0 8.0 11.2 14.0 16.0
BTU/h
23,900 27,300 38,200 47,800 54,600
Sound Pressure level
(Cooling / Heating)
dB(A)
48 / 50 48 / 50 52 / 52 53 / 53 54 / 55
Sound Power level
(Cooling / Heating)
dB(A)
65 / 67 65 / 67 69 / 69 70 / 70 71 / 71
Unit Dimensions
(H×W×D)
mm
996×940×340 996×940×340 1,416×940×340 1,416×940×340 1,416×940×340
Net weight
kg
68 69 98 98 98
Operation condition temperature range
•Coolingmode:-15°C~46°CDB•Heatingmode:-20°C~18°CWB/-20°C~24°CDB
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.
OI_00_301034_EU.indb 85 2018/1/30 14:00:01