25
■
Technical Data
● EAIRC-MJ Types
HP 4 8 10 14
Air Curtain PAW-10EAIRC-MJ PAW-15EAIRC-MJ PAW-20EAIRC-MJ PAW-25EAIRC-MJ
Air ow type
Jetow
Air volume (high) m³/h 1800 2700 3600 4500
Air volume (medium) m³/h 1500 2300 3000 3800
Air volume (low) m³/h 1200 1900 2500 3100
Air ow length (A) m 1.0 1.5 2.0 2.5
Heating capacity (nominal) kW 11.4 25.0 31.5 31.5
Cooling capacity (nominal) kW
*1
9.2 17.5 23.1 24.4
Heating capacity with air in 20 °C, air
out 40 °C
kW 11.9 17.9 23.9 29.9
Heating capacity with air in 20 °C, air
out 35 °C kW 8.9 13.4 17.9 22.4
Heating capacity with air in 20 °C, air
out 30 °C kW 5.9 8.9 11.9 14.9
Max inst. height in good conditions m 3.5 3.5 3.5 3.5
Max inst. height in normal conditions m 3.1 3.1 3.1 3.1
Max inst. height in bad conditions m 2.7 2.7 2.7 2.7
Refrigerant R410a
Hot gas temperature °C 70 70 70 70
Pressure bar 45 45 45 45
Tubing Gas mm 15.88 19.05 22.22 22.22
Tubing Liquid mm 9.52 9.52 9.52 9.52
Fan 230V/50Hz/1/N/PE
Fan type EC EC EC EC
Operating current (high) A 2.10 2.80 4.20 4.90
Electrical consumption (high) kW 0.44 0.59 0.89 1.03
Operating current (med) A 0.80 1.10 1.60 1.90
Electrical consumption (med) kW 0.17 0.23 0.34 0.40
Operating current (low) A 0.30 0.40 0.60 0.70
Electrical consumption (low) kW 0.06 0.08 0.12 0.14
Protecting fuse A M16A M16A M16A M16A
Noise dB(A) 40–55 40–56 40–57 40–58
Dimensions (L/H/D): mm 1210 x 260 x 590 1710 x 260 x 590 2210 x 260 x 590 2710 x 260 x 590
Weight kg 70 100 138 160
Mini ECOi with air out 40 °C U-4LE1E5/8
*2
U-6LE1E5/8
*2
-- --
Mini ECOi with air out 35 °C U-4LE1E5/8
*2
U-4LE1E5/8
*2
U-6LE1E5/8
*2
--
Mini ECOi with air out 30 °C U-4LE1E5/8
*2
U-4LE1E5/8
*2
U-4LE1E5/8
*2
U-5LE1E5/8
*2
ECOi with air out 40 °C All models All models All models All models without 8HP
ECOi with air out 30 °C or 35 °C All models All models All models All models
GHP all temperatures All models All models All models All models
Allcombinationsunderratedconditions.Heating:Outdoor+7°CDB/+6°CWB,Indoor+20°CDB.Incaseofloweroutdoor
temperatures a higher capacity outdoor unit model may be necessary
*1RatedConditionsCooling:Outdoor+35°CDB,Indoor+27°CDB/+19°CWB,Dischargetemp.≥ 16 °C.
*2 Or bigger size.