Operating Instructions
Air-to-Water Heatpump
Model No.
Indoor Unit
Outdoor Unit
WH-SDC09C3E8 WH-UD09CE8
WH-SDC12C9E8 WH-UD12CE8
WH-SDC14C9E8 WH-UD14CE8
WH-SDC16C9E8 WH-UD16CE8
© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2010.
Unauthorized copying and distribution is a violation
of law.
ENGLISH
ENGLISH
Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Before operating the unit, make sure the installation has been carried out correctly by authorized dealer correctly and
precisely following the installation instructions given.
2 ~ 11
2 ~ 11
FRANÇAIS
FRANÇAIS
Avant d’utiliser l’appareil, lisez ce mode d’emploi dans son intégralité et conservez-le pour toute référence ultérieure.
Avant de faire fonctionner l’unité, assurez-vous que l’installation a été correctement réalisée par un revendeur agréé
et dans le strict respect des consignes d’installation fournies.
12 ~ 21
12 ~ 21
ESPAÑOL
Antes de utilizar la unidad, sírvase leer atentamente estas instrucciones de funcionamiento y conservarlas como
futuro elemento de consulta.
Antes de operar la unidad asegúrese de que la instalación haya sido realizada correctamente por un instalador
autorizado, siguiendo de forma correcta y precisa las instrucciones de instalación dadas.
22 ~ 31
22 ~ 31
DEUTSCH
Bevor Sie das Gerät in Betrieb nehmen, lesen Sie bitte diese Bedienungsanleitung aufmerksam durch und bewahren Sie
sie für die künftige Verwendung auf.
Vor der Inbetriebnahme dieses Geräts ist sicherzustellen, dass die Montage durch einen autorisierten Händler
fachgerecht entsprechend der Installationsanleitung durchgeführt wurde.
32 ~ 41
32 ~ 41
ITALIANO
Prima di utilizzare l’unità si prega di leggere attentamente le istruzioni e di conservare questo opuscolo per potervi
fare riferimento in futuro.
Prima di far funzionare l’unità, assicurarsi che l’installazione sia stata eseguita correttamente da un rivenditore
autorizzato e seguendo precisamente le istruzioni date per l’installazione
42 ~ 51
42 ~ 51
NEDERLANDS
Lees voor u het apparaat gebruikt deze gebruiksaanwijzing grondig en bewaar deze voor toekomstig gebruik.
Controleer, voor u de unit in gebruik neemt, dat de installatie goed is uitgevoerd door een of ciële dealer en dat dat
nauwkeurig is gedaan volgens de verstrekte instructies voor de installatie.
52 ~ 61
PORTUGUÊS
Antes de ligar a unidade, leia cuidadosamente este manual de utilização e guarde-o para futura referência.
Antes de colocar a unidade em funcionamento, ceritifque-se que a instalação foi feita correctamente por um
fornecedor autorizado e que seguiu com precisão as instruções de instalação dadas.
62 ~ 71
EΛΛΗΝΙΚΆ
Προτού θέσετε τη μονάδα σε λειτουργία, διαβάστε προσεκτικά αυτές τις οδηγίες χρήσης και φυλάξτε τις για μελλοντική αναφορά.
Πριν θέσετε σε λειτουργία τη μονάδα, βεβαιωθείτε ότι η εγκατάσταση έχει διεξαχθεί κανονικά από εξουσιοδοτημένο
αντιπρόσωπο, ο οποίος έχει ακολουθήσει σωστά και πιστά τις δοθείσες οδηγίες.
72 ~ 81
БЪЛГАРСКИ
БЪЛГАРСКИ
Преди да задействате климатика, прочетете внимателно инструкциите за употреба и ги запазете за бъдещи справки.
Преди да използвате устройството се уверете, че монтажът е извършен правилно и прецизно от оторизиран дилър,
като са спазвани инструкциите за монтаж.
82 ~91
82 ~91
0.2
0.40
0.30.1
MPa
TIMER OUTDOOR
HEAT
SETTING
STATUS
PUMPDW
BOOSTER
QUIET
TANK
WATER OUTLET
C
C
OFF
/
ON
HEATER
OPERATION
FORCE
HEATER
ACTUAL
TIMER
1
MONTUEWEDTHU FRI SATSUN
SOLAR REMOTE
NOT AVAILABLE
2 3 4 56
ON
OFF
COOL

Other manuals for Panasonic WH-SDC16C9E8

Questions and Answers

  • S
    Steven ArmstrongSep 23, 2025
    What does Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) mean on my Panasonic WH-SDC16C9E8?
    • M
      Matthew DanielSep 23, 2025
      An Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) on your Panasonic Heat Pump can be caused by: * Faulty connector connection. * Faulty sensor. * Faulty outdoor unit PCB (main). The temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error during startup and operation of cooling and heating.
  • M
    Marc FoxAug 23, 2025
    What causes a Compressor Overheating (F20) error in my Panasonic WH-SDC16C9E8 Heat Pump?
    • J
      John KirbyAug 23, 2025
      A Compressor Overheating (F20) error in your Panasonic Heat Pump can be triggered by: * A faulty compressor tank temperature sensor. * Closed 2/3 way valve. * Refrigerant shortage (refrigerant leakage). * Clogged expansion valve or strainer. * Faulty outdoor unit PCB (main). * Faulty compressor. This error occurs during cooling and heating when the compressor tank temperature sensor detects a temperature above 112°C.
  • A
    Amber DanielsAug 25, 2025
    What does it mean when my Panasonic WH-SDC16C9E8 Heat Pump displays Outdoor High Pressure Abnormality (H64)?
    • J
      James OlsonAug 26, 2025
      An Outdoor High Pressure Abnormality (H64) on your Panasonic Heat Pump indicates a problem with the outdoor high pressure sensor. This can be due to: * A faulty connector connection. * A faulty sensor. * A faulty outdoor unit PCB (main). The system detects this abnormality during cooling and heating when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc.
  • D
    Dwayne FloresAug 27, 2025
    Why am I getting an Outdoor High Pressure Switch Activate (F12) error on my Panasonic WH-SDC16C9E8?
    • A
      Andrew GarciaAug 27, 2025
      An Outdoor High Pressure Switch Activate (F12) error on your Panasonic Heat Pump indicates that the outdoor high pressure switch has been activated. This can be due to: * Dust accumulation on the outdoor unit heat exchanger. * Air short circuit at the outdoor unit. * A faulty water pump. * Insufficient water flow rate in the system. * Water leak in the system. * A closed 2/3 way valve. * A clogged expansion valve or strainer. * Excessive refrigerant. * A faulty outdoor high pressure sensor and switch. * A faulty outdoor unit PCB. This occurs during cooling and heating operation when the outdoor high pressure switch detects pressure at 4.5MPa and above.
  • A
    Amy CaseAug 27, 2025
    What does Input Over Current Detection (F16) mean on my Panasonic WH-SDC16C9E8 Heat Pump?
    • S
      Sonya RandallAug 27, 2025
      Input Over Current Detection (F16) on your Panasonic Heat Pump means that the outdoor current is too high. This can be caused by: * Excessive refrigerant. * Faulty outdoor unit PCB (main). During cooling and heating operation, this error is triggered when the current transformer (CT) in the outdoor unit PCB detects outdoor current above 10.6A.
  • E
    Erika PopeSep 18, 2025
    What does Indoor Water Inlet Temperature Sensor Abnormality (F37) mean on my Panasonic WH-SDC16C9E8 Heat Pump?
    • N
      Nicholas LoveSep 18, 2025
      An Indoor Water Inlet Temperature Sensor Abnormality (F37) on your Panasonic Heat Pump can be caused by: * Faulty connector connection. * Faulty sensor. * Faulty indoor unit PCB (main). The temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error during startup and operation of cooling and heating.
  • M
    masseyemilySep 15, 2025
    Why is my Panasonic Heat Pump showing Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23)?
    • S
      Susan JonesSep 15, 2025
      An Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) on your Panasonic Heat Pump can be caused by: * Faulty connector connection. * Faulty sensor. * Faulty indoor unit PCB (main). The temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error during startup and operation of cooling and heating.
  • G
    glenndavidSep 16, 2025
    What causes a Compressor Tank Temperature Sensor Abnormality (H15) in a Panasonic WH-SDC16C9E8?
    • M
      Matthew WardSep 17, 2025
      A Compressor Tank Temperature Sensor Abnormality (H15) in your Panasonic Heat Pump can be caused by: * Faulty connector connection. * Faulty sensor. * Faulty outdoor unit PCB (main). The temperatures detected by the compressor tank temperature sensor are used to determine sensor error during startup and operation of cooling and heating.
  • S
    Sharon HarringtonSep 7, 2025
    What causes a Compressor Rotation Failure (F14) in my Panasonic WH-SDC16C9E8 Heat Pump?
    • M
      michaelfriedmanSep 7, 2025
      A Compressor Rotation Failure (F14) in your Panasonic Heat Pump can be attributed to: * Compressor terminal disconnect. * Faulty outdoor unit PCB (main). * Faulty compressor. The system checks the compressor running condition through the position detection circuit to detect this failure.
  • M
    michaeltownsendSep 3, 2025
    Why is my Panasonic WH-SDC16C9E8 showing Unspecified Voltage between Indoor and Outdoor (H95)?
    • J
      jonathanwhitakerSep 4, 2025
      An Unspecified Voltage between Indoor and Outdoor (H95) error on your Panasonic Heat Pump may be due to: * Insufficient power supply. * Faulty outdoor unit PCB (noise filter/main). The supply power is detected for its requirement by the indoor/outdoor transmission.

Summary

Safety Precautions

General Safety Warnings and Symbols

Explains safety warning signs and symbols used in the manual for user safety.

Indoor and Outdoor Unit Safety

Safety guidelines for operating and handling indoor and outdoor units to prevent injury.

Safety Precautions - Power and Control Panel

Power Supply Safety

Precautions for safe electrical connection and usage of power supply to prevent hazards.

Control Panel Safety

Safety measures for operating and maintaining the control panel to avoid shock or damage.

Control Panel

Control Panel Overview

Identifies and describes the buttons and indicators on the control panel.

Setting Current Day and Time

Instructions for setting the current day and time on the control panel.

Special Functions Setup

Select Functions and Set Timer

Guide to selecting functions and setting timers for special operations.

Operation Modes and Functions

Details on various operation modes and their descriptions.

Sterilization Function Setup

Instructions for setting up and performing the sterilization function.

Basic Operation

Unit Power Control

Procedure for switching the unit on and off.

Operation Mode Selection

Guide on choosing between HEAT, COOL, TANK, and combined modes.

Quiet Operation Mode

How to activate quiet mode for reduced noise operation.

Backup Heater Operation

Instructions for enabling and using the backup heater for extra capacity.

System Status Check

Steps to enter and use the system status check mode.

Advanced Operation

System Setting Mode

Guide to advanced settings for operation and temperature parameters.

Water Temperature Shift Settings

Procedure for adjusting the water temperature shift settings.

Weekly Timer Setting

Timer Display Explanation

Explanation of the timer display elements and indicators.

Setting Timer Day and Time

Step-by-step guide to setting timer programs for days and times.

Timer Management Functions

Instructions for adding, modifying, enabling, checking, and canceling timers.

Indoor Unit Maintenance

Indoor Unit Cleaning

Guidelines for cleaning the indoor unit safely and effectively.

Control Panel Cleaning

Instructions for cleaning the control panel gently.

External Filter Maintenance

Procedure for cleaning the external filter to maintain performance.

Outdoor Unit Care and Inspection

Advice on maintaining the outdoor unit, including ventilation and inspections.

Extended Non-Use and Service Criteria

Handling the unit during non-use and conditions requiring dealer service.

Troubleshooting

Normal Operation Symptoms

Common sounds or operations that are normal and not malfunctions.

System Difficulties and Causes

Explanation of common heating/cooling issues and their potential causes.

Pre-Servicing Checks

List of checks to perform before calling for professional servicing.

Error Codes and Indicators

Information on interpreting operation LED blinking and error codes.

Force Heater Mode Usage

Details on using the backup heater in force heater mode.

Information on Disposal

Old Equipment Disposal (EU)

Information on the collection and disposal of used electrical and electronic products in the EU.

Business User Equipment Disposal

Guidance for business users on discarding electrical and electronic equipment.

Disposal Outside European Union

Information on proper disposal methods for countries outside the European Union.

Panasonic WH-SDC16C9E8 Specifications

General IconGeneral
Heating capacity16.00 kW
Energy efficiency class (Heating)A++
RefrigerantR32
Cooling capacity14 kW
Operating temperature range (Heating)-20°C to +35°C
Operating temperature range (Cooling)+10°C to +46°C
Sound Power Level Outdoor65 dB(A)