16.5.27 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe
temperature sensor are used to determine sensor error.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.