Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify
F41 PFC control 4 times occurrence within 10
minutes
Voltage at PFC
F42 Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43 Outdoor defrost sensor abnormality Continue for 5 sec.
Outdoor defrost sensor (defective or
disconnected)
F45 Indoor water outlet temperature sensor
abnormality
Continue for 5 sec.
Water outlet temperature sensor
(defective or disconnected)
F46 Outdoor Current Transformer open
circuit
Insufficient refrigerant
Outdoor PCB
Compressor low
F48 Outdoor EVA outlet temperature sensor
abnormality
Continue for 5 sec.
Outdoor EVA outlet temperature sensor
(defective or disconnected)
F49 Outdoor bypass outlet temperature
sensor abnormality
Continue for 5 sec.
Outdoor bypass outlet temperature
sensor (defective or disconnected)
F95 Cooling high pressure overload
protection
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB