EasyManua.ls Logo

Panasonic WH-UD09HE8 - Page 204

Panasonic WH-UD09HE8
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
204
16.5.44 Outdoor Defrost Temperature Sensor Abnormality (F43)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost
temperature sensor are used to determine sensor error.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.
Check the outdoor defrost temperature sensor:
- Plug out connector from the outdoor unit PCB (main)
- Measure the resistance of the outdoor defrost
temperature sensor
- Defect in outdoor defrost
temperature sensor
- Replace the outdoor defrost
temperature sensor
Yes
Is the measured resistance of the
outdoor defrost temperature sensor
matches the value specified in its
characteristic chart?
No
Check the CN-TH2 connector connection:
- Turn OFF the power
- Check the connector connection
- Connector poor contact
- Correct the connection
No
Is the CN-TH2 connector
connection normal?
- Defect in outdoor unit PCB (main)
- Replace the outdoor unit PCB (main)
Yes
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Caution

Table of Contents

Other manuals for Panasonic WH-UD09HE8

Related product manuals