22 External Control Connection Terminal
(SPOT MONITOR CONTROL IN/RECOVER IN/ALARM
CONTROL OUT/REMOTE OUT)
.
SPOT MONITOR CONTROL IN
The terminals of the Spot Monitor Control In are used
to connect the intercom or alarm sensors for the spot
monitoring by making a short circuit of terminal 1,2, 3 or 4.
When the Camera Extension Unit is used, the spot moni-
toring is proceeded for terminal 5, 6 and 7 of the camera
extension unit.
If the terminal
1
is shorted by intercom or alarm sensors,
the camera No.1 is selected and its picture is observed on
the monitor.
The picture of the camera
No.2,
3 or 4 (5, 6 or 7 when the
Camera Extension Unit is used.) can be observed in the
same manner.
Note:
The voltage of short circuit for the terminal should be 0 -
0.2 volt when the intercom or alarm sensor is activated.
.
l RECOVER IN
To reset the spot monitor picture of the desired camera
and back to the sequence operation, supply the reset
signal from the time lapse
VTR
to this terminal.
l ALARM CONTROL OUT
The terminals of the Alarm Control Out are used to connect
the buzzer or chime for sounding when the terminals of
the Spot Monitor Control In is (are) shorted by intercom or
alarm sensor.
ALL MODE-GND Connection
The connected buzzer or chime will sound at both
positions of the Mode Selection Switch (2) when the
intercom or alarm is activated.
STANDBY-GND Connection
The connected buzzer or chime will sound when the
Mode Selection Switch (2) is positioned at STANDBY
and the intercom or alarm is activated,
l REMOTE OUT Connection
The terminals for the Remote Out are used to connect the
Spot Monitor Control In on another monitor for the Spot
Monitoring by short circuit of terminal
1,2,3
or 4 when the
two video monitors are connected,
The RESET out terminal is used to connect the RECOVER
input terminal on another monitor.
The terminals for the Remote Out are also used to connect
the Remote In terminals on the panning control by short
circuit of terminal 1, 2, 3 or 4 when the video monitor
is connected with Remote Control Unit for Auto Panning
Head.
The power rate of the alarm should be up to DC
24V,
max.
1
OOmA.
If the power capacity of the remote is less than
1
OOmA
at
DC
24V,
the remote load can be connected at the terminal
of Remote directly.
If the power capacity of the alarm is more than
1
OOmA
at
DC
24V,
the relay circuit should be used for the remote
load.
-
.
CONNECTIONS
Cautions:
1.
Keep the Power Switch of the monitor, optional Camera
Extensron
Unit and optional Remote Control
Unrt
in the
OFF position during
connectlon.
If the power of these units are ON during connection, the
camera will not function due to the protection circuit for
misconnection.
2.
Connect only the specified cameras WV-BL90 or WV-71,
If other type of camera is connected, the Mini camera
system will not perform due to the protection circuit for
wrong camera.