MPC2000D Issue 2 22/4/98 Page 25
On the right hand side of the page is the default setting,
E=Enabled D=Disabled.
T=Trip A=Alarm
AR=Auto-Reset PR=Panel Reset
R=Remote Reset
The above options are provided individually for all of the following MPC2000D protective and control functions:
Function T A AR PR R
Maximum Start Time D E D E E
Too Many Starts D D D E E
Undercurrent Pre-Alarm D E D E E
Undercurrent Trip D D D E E
Load Increase Alarm D E D E E
Low Set Overcurrent E E D E E
High Set Overcurrent D D D E E
Thermal Pre-Alarm D E D E E
Thermal Trip E E D E E
Unbalance Alarm D E D E E
Unbalance Trip E E D E E
Undervoltage Trip D E D E E
Overvoltage Pre-Alarm D E D E E
Overvoltage Trip E E D E E
Phase Loss E E D E E
Phase Sequence E E E E E
Temp 1 Channel Pre-Alarm D D D E E
Temp 1 Channel Trip D D D E E
Temp 2 Channel Pre-Alarm D D D E E
Temp 2 Channel Trip D D D E E
Temp 3 Channel Pre-Alarm D D D E E
Temp 3 Channel Trip D D D E E
Earth Fault Pre-Alarm D E D E E
Earth Fault Trip E E D D D
Serial Port Failure D D E E E
Internal Relay Failure D E D D D
Emergency Stop D D D E E
Control Circuit Open D D D E E
Welded Contactor D D D E E
External Fault 2 D D D E E
External Fault 3 D D D E E