Lubrication:
Any grease nipple (All other items are “sealed for life” and require no lubrication)
Function checks:
Overall barrier structure is plumb
Lubricate any parts that need lubricating see section “Lubrication above
Gearbox oil level
Function of manual release
Torque setting on control unit (If obstacle detection has been used)
•Obstacle detection effectiveness (measure forces: not a legal requirement)
Overall function/condition of motor/gearbox
Function and condition of safe edges
Photocells internal and external
Sealing of photocell covers and cable entry
Wire terminations in control panel
Sealing of control unit cover and cable entries
Condition of all wiring and junction boxes
Function of all controls transmitters, loop and intercoms
•Security and effectiveness of all earth connections
Test earth fault loop resistance and RCD function (MCB is preferred)
Reassess and check the ongoing validity of the hazard assessment
Performance tests:
Force Test (Not a legal requirement but advisory)
Check that the manual release is working
Ensure that the barrier is running smoothly
Check Flashing Beacon is working (If fitted)
Check any safety devices fitted are working as designed (Loops/Photocells/Light Curtains etc.)