EasyManua.ls Logo

Parking Facilities PF9700 - Input Parameter Configuration; Input Functions and Contact Types

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
in
Parking and access control equipment manufactured in the UK
PF9700 Automated Hinge Gate
Every input/output is highly configurable, and can be changed from its default/state use. The below is a guide to what they can
be changed to and the effect of this change. The logic behind this is as follows:
On the wiring diagram each terminal has an input number this is noted as “IN6" for example. To change this or other values the
table below quotes P. 0 the “ ” needs to be replaced with the input/output you wish to configure. So as an example if we 5x x
wanted to change input “6" (terminals 82&83) we would replace the “ ” with “ " making it “P. 0". Also note that the number x 6 65
following “P.” (in our example “ ") denotes we are dealing with and “input” if instead we wanted to deal with an “output” we 5
would replace the “ " with a “ ". The below is a brief summary of common changes but there are MANY more options than 5 7
listed here, for a full list please contact the supplying company.
Inputs
Parameter
Unit Range
Function
Description/Value of Parameter
P.5x0
0 ..... 18
Input Functions
With this parameter the functionality for parameter x is set.
0: Input deactivated
1: OPEN command
2: Single channel / pull switch
3: Permanent open command
4: Stop command
5: Safety B
6: Jog mode / Automatic switch
7: Close command
8: Door locking in end position
9: Cross traffic input
10: Deactivation input
11: Limit switch input
14: Safety A
15: Simulation of foil key pad
16: Safety C
17: Door drive to intermediate stop / partial open
18: External detector
Notes Area...
P.5x2
0 ..... 1
Contact Type
Specifies the contact type of the switch which is connected to the input.
0: N.O., Normally open
1: N.C., Normally closed
P.5x4
0 ..... 7
Hold-open time /
Priority
This parameter specifies if and which hold-open time / forced closing time runs after
activating the input.
Notes Area...
0: Without auto close time
1: With auto close time (P.010 or P.011)
2: With minimum auto close time (P.015)
3: No auto close time until a CLOSE command is given.
4: Auto close time as used before with the last open command.
5: The auto close time is stopped after activating in end position door OPEN
and will go on after deactivation. By reversing during closing the min. auto
close time is running.
6: With Priority 1 (highest Priority: like PULSE OPEN)
7: With Priority 2 (second highest Priority: like pull switch)
Outputs
P.7x0
0 ..... 27
Switching
Condition of
output relay
The selected output relay is energized under the following conditions:
Notes Area...
0: If End position Door OPEN was reliably detected
1: If End position Door OPEN was not reliably detected
2: If End position Door CLOSE was reliably detected
3: If End position Door CLOSE was not detected
4: If there is no fault condition or emergency stop, controller in Automatic mode
5: Courtyard light function, during every OPEN and CLOSE move with 10 turn-
off delay after opening. 6: Command forwarding
This setting involves additional setting under P.7xF.
7: During each OPEN and CLOSE move
8: During each OPEN and CLOSE move and during active clearing time.
9: Forward external door release (e.g., airlock operation)
10: Forward external door locking (e.g., airlock operation)
11: Magnet voltage during closing and in end position close
13

Other manuals for Parking Facilities PF9700

Related product manuals