20
ChUP Value that equates to -9999 to 9999* 100
upper chart division
ChLO Value that equates to -9999 to 9999 0
Lower chart division
HySt Hysteresis or Switch 0 to 200* 3
differential for outputs
in units, not percent
(will show only if outputs present)
dFF Display Filter Factor 1 to 10 1
Filters display for input
noise. Higher number
means more filtering.
ALC Alarm Changes On = Allowed/Enable On
Determines if output OFF = Disable
setpoints can be changed
in the RUN mode
* The range shown corresponds to no decimal position. If dPOS is 1, 9999 becomes 999.9, 200 becomes 20.0, etc.
CHART SECTION OF PROGRAM MODE
- CHAr
(There is only one parameter in this section)
PARAMETER PARAMETER DEFAULT
CODE DESCRIPTION SETTINGS OR RANGE SETTING
ChSP Chart Speed OFF = off - don't rotate 24Hr
8Hr = 8 hours
12Hr = 12 hours
24Hr = 24 hours
48Hr = 48 hours
7dAy = 7 days
**COMMUNICATION PARAMETER - CP
(There is only one parameter in this section) Only seen if optional communications is ordered.
PARAMETER PARAMETER DEFAULT
CODE DESCRIPTION SETTINGS OR RANGE SETTING
CAd Communication Address 0 to 247 0
NOTE: Communications Bit Rate is fixed at 9600 baud.
w ww . . co m