CONDENSE RECOVERY
1. Regardless of the type of application, a certain amount
of condense is generated inside the steam distributor.
This condense must be disposed of to avoid obstructing
the steam flow. If the distributor is positioned higher
than the humidifier and the steam tube does not
generate siphons, condense recovery may not require
installation (e.g. Fig. 43).
Fig. 43
2. If the distributor is positioned higher than the humidifier and the steam tube generates a siphon
(e.g. Fig. 44), the condense recovery must be installed, directly discharging in appropriate
cylinder sleeve of the humidifier (Fig. 45) or in a water collection well. The condense recovery
is made connecting the 10 mm sleeve of the distributor to the PEGO UMITUBODN10 tube for
this type of application. In the path of the condense recovery tube from distributor to humidifier
or from distributor to well, a siphon must be made with full turn of 200 mm minimum diameter;
the siphon must be charged with water prior to installation.
This will prevent steam exiting the condense recovery tube (Fig. 44).
Fig.44 Fig. 45
3. If the distributor is positioned below the humidifier, as usually happens in OEM series
humidifiers installations, it is essential to recover condense discharging in a water collection
well.