PLUS 100 AB
Page 20
Rev. 01-08
MANUALE D’USO E MANUTENZIONE
LEVEL 2 PROGRAMMING (Installer level)
To access the second programming level press the UP (t) and DOWN (u) keys and the
LIGHT key simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP (t) and DOWN (u) keys.
When the parameter has been selected it is possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down and pressing the (t) or (u) key.
4. When configuration settings have been completed you can exit the menu by pressing
the (t) and (u) keys simultaneously and keeping them pressed until the room
temperature value reappears.
5. Changes are saved automatically when you exit the configuration menu.
6. Press the STAND-BY key to enable electronic control.
VARIABLE MEANING VALUES DEFAULT
dFr
Real-time defrost enable
With d0=0 and dFr=1 it is possible to set up to 6 defrosts
in real time in a day by using the parameters dF1…dF6
0 disabled
1 enabled
0
dF1…dF6
Programming defrost times
It is possible to set up to 6 defrosting times
00:00:00 -
23:50:00
--
STS
Freezing SET
Manages the switch from cooling to freezing in programs
PR3 and PR6.
-45 - +45 °C -10°C
CHAP. 5 – Parameter programming