PLUS 100 AB
Page 21
Rev. 01-08 MANUALE D’USO E MANUTENZIONE
LIST OF LEVEL 2 VARIABLES (Installer level)
VARIABLE MEANING VALUES DEFAULT
AC
Door switch input status
0= normally open
1= normally closed
0
F3
Fan status with compressor off
0 = Fans working
continuously
1 = Fans working only when
compressor working
1
F4
Fan pause during defrost
0 = Fans working during
defrost
1 = Fans not working during
defrost
1
F6
Air re-circulate fan activation
The fans come on for a time defined by F7
if they have not come on for the time F6.
If the moment of activation coincides with
defrosting there is a wait until defrosting
has been completed
0 – 240 min
0 (function
deactivated)
F7
Air re-circulate fans activation duration
Fan operation time for F6
0-240 sec 0:00:10
dE
Sensor presence
By excluding the evaporator sensor
defrosts occur cyclically according to a
period d0 and end when an external device
that closes the remote defrost contact trips
or when time d3 expires
0 = evaporator sensor present
1 = evaporator sensor absent
0
dE1
Product sensor presence
With dE1=1 it is possible to disconnect the
product sensor without an error warning
and cooling is time-based only
0 = product sensor present
1 = product sensor absent
0
dC
Remote defrost input status
0 = NO
1 = NC
0 = NA
d1
Defrost type, cycle-inversion (hot gas) or
by heating element
1= hot gas
0= element
0
d4
End-of-cooling defrost
This parameter decides whether, at the
end of the cooling phase, a defrost has to
be carried out immediately (d4=0) or if the
defrosts follow the settings independently
(d4=1).
If d4=0 a defrost will in any case take place
even if timed defrosts are enabled
0 – 1 default 0
Ad
Network address for connection to the
TeleWIN supervision system
0 - 31 0
Ald
Minimum and maximum temperature
signalling and alarm display delay
1…240 min 2:00:00
C1
Minimum time between shutdown and
subsequent switching on of the
compressor.
0…15 min 0 min
CAL
Cold room sensor value correction
-10…+10 0
CAS
Skewer sensor value correction
-10…+10 0