PLUS 100 AB
Page 22
Rev. 01-08
MANUALE D’USO E MANUTENZIONE
Pc
Compressor protection contact status
0 = NO
1 = NC
0 = NO
doC
Compressor safety time for door
switch: when the door is opened the
evaporator fans shut down and the
compressor will continue working for time
doC, after which it will shut down.
0…5 minutes 0
Fst
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
read by the evaporator sensor is higher
than this value.
-45…+45°C +45°C
tA
NO – NC alarm relay switching
=activates when alarm is on
1=deactivates when alarm is
on
1
rA
Control relay door anti-fogging element
0=alarm relay
1=anti-fogging element on
0
in2
Man in cold room alarm
Select input INP2 on the board as end of
remote defrost or as man in cold room
alarm (contact NC).
0 = remote defrost end
1 = man in room alarm
0
Lic
Lower temperature set-point limit
-45.. LSc -45°C
LSc Upper temperature set-point limit
Lic..+45 +45°C
dMY
Day-month-year setting
day-month-year -
hMS
Clock setting
Hour–min-sec -
CHAP. 5 – Parameter programming