9.6.2 Mounting and Installation
Startup the Pentek Assistant
Apply power to the unit, and follow the steps in section
9.6.3 after the Drive’s screen is lit.
9.6.3 Using the Pentek Assistant
Apply power to the unit and follow the steps in Section
9.6.4 for changing operation parameters, use the steps
below to run the Pentek Assistant.
1. Use the MENU key to access the Menu List.
2. Select Assistants
3. Select Pentek Assistant.
4. Follow the screen instructions to configure the
system.
Table 9-7: PPC5 Parameters Changed Relative to PID Control Defaults
SECTION 9: PPC Series 50/60 Hz Variable Frequency Drives
Parameter Code Pentek
®
Code
1002 EXT2 Commands 8-Keypad
1102 EXT1/EXT2 SEL EXT2
1301 Minimum AI1 20%
1401 RELAY OUTPUT 1 SUPERV1 OVER
1404 RO 1 ON DELAY 10 S (above ground)
60 S (submersible)
1405 RO 1 OFF DELAY 2 S
1601 Run Enable Not SeL
1605 USER PAR SET CHG 3-DI3
2001 Minimum Speed User defined (above ground)
0 (submersible)
2002 MAXIMUM SPEED SYNC
2202 ACCELER TIME 15 SEC (above ground)
1 SEC (submersible)
3001 AI<MIN FUNCTION 1-FAULT
3003 EXTERNAL FAULT 1 1-DI6
3004 EXTERNAL FAULT 2 5-DI5
3006 MOT THERM TIME 500 SEC (above ground)
350 SEC (submersible)
3007 MOT LOAD CURVE 100% (above ground)
112% (submersible)
3013 UNDERLOAD FUNC 1-FAULT
3014 UNDERLOAD TIME 10S
3022 AI2 FAULT LIMIT 10%
3201 SUPERV 1 PARAM 103-OUTPUT
FREQ
3202 SUPERV 1 LIM LO 60
3203 SUPERV 1 LIM HI 60
3401 SIGNAL 1 PARAM 104-CURRENT
Parameter Code Pentek Code
3402 SIGNAL 1 MIN 0
3404 OUTPUT 1 DSP FORM 5-+0.0
3405 OUTPUT 1 UNIT 1 – AMPS
3408 SIGNAL 2 PARAM 102-SPEED
3411 OUTPUT 2 DSP FORM 4-+0
3412 OUTPUT 2 UNIT 7 – RPM
3415 SIGNAL 3 PARAMETER 128-PID 1 SETPNT
3418 OUTPUT 3 DSP FORM 1 - ± 0.0
3419 OUTPUT 3 UNIT 25 – PSI
4001 GAIN 1.0
4002 INTEGRATION TIME 2.0
4006 UNIT 25 – PSI
4010 SET POINT SEL 0 – KEYPAD
4011 INTERNAL SETPOINT USER DEFINED
4016 ACT1 INPUT 1-AI2
4017 ACT2 INPUT 1-AI2
4022 SLEEP SELECTION 7 – INT
4024 PID SLEEP DELAY 10 SEC
4027 PID 1 PARAM SET 3-DI3
4102 INTEGRATION TIME 1.0S
4106 UNIT 25-PSI
4109 100% Value per 4009
4110 SET POINT SEL 19-INTERNAL
4111 INTERNAL SETPOINT PER 4011
4122 SLEEP SELECTION 7-INT
4123 PID SLEEP LEVEL per 4023
4124 PID SLEEP DELAY 10SEC
4125 WAKE-UP DEV per 4025