71
9.6.1 Description of Information Required
by the Pentek Assistant
9905 Motor Nom Voltage: This is the nominal voltage
stated on the motor nameplate. If the motor is rated
for operation at multiple voltages, select the voltage
nearest the utility voltage. Ensure the motor connections
correspond to the voltage selected.
9906 Motor Nom Current: This is the nominal current
found on the motor nameplate. Do not use service
factoramps.
9907 Motor Nom Freq: This is the nominal frequency
found on the motor nameplate.
9908 Motor Nominal Speed: This is the nominal speed
found on the motor nameplate. Use the number on the
motor nameplate. Do not enter 3600, 1800, etc.
9909 Motor Nom Power: This is the nominal horsepower
found on the motor nameplate. Do not include service
factor unless the service factor is greater than 1.15.
2001 Min Speed (Required for Subs only): This is the
minimum speed the motor is allowed to run. This
minimum is set to prevent damage to the motor thrust
bearings. Refer to motor literature to determine setting.
4011 Internal Setpoint: This is the pressure that the
system will maintain.
4009 100% Value: This is the full scale reading of the
transducer. The 100% Value of a 200PSI transducer
is200PSI.
4023 PID Sleep Level: Operation below this rpm will
cause the drive to stop. Must never be below the shut-off
head RPM.
4025 Wake-Up Dev: This is the pressure drop that will
trigger the drive to restart. For example, if the set point is
60 PSI and the Wake-Up Deviation is 10 PSI, the drive will
restart at 50 PSI.
Parameter Code Pentek Code
1002 Ext2 Commands Keypad
1102 EXT1/EXT2 Sel EXT2
1301 Minimum AI1 20%
1601 Run Enable Not Sel
1805 DO Signal Superv1 Over
1806 DO On Delay 10 Seconds (Above Ground)
1806 DO On Delay 60 Seconds (Submersible)
1807 DO Off Delay 2 sec
2001 Minimum Speed 0 (Above Ground)
2001 Minimum Speed User Defined (Submersible)
2002 Maximum Speed Sync
2202 Accel Time 1 5 sec (Above Ground)
2202 Accel Time 1 1 sec(Submersible)
3001 AI<Min Fault
3003 External Fault 1 DI5
3006 Mot Therm Time 500 sec (Above Ground)
3006 Mot Therm Time 350 sec (Submersible)
3007 Mot Load Curve 100% (Above Ground)
3007 Mot Load Curve 112% (Submersible)
3013 Underload Function Fault
3014 Underload Time 10 sec
3022 AI2 Fault Limi 10%
3201 Superv 1 Param Output Freq
3202 SuperV 1 Lim Lo per 9907
3203 SuperV 1 Lim Hi per 9907
Parameter Code Pentek Code
3401 Signal 1 Param Current
3405 Output 1 Unit A
3408 Signal 2 Param Speed
3412 Output 2 Unit RPM
3415 Signal 3 Param PID 1 FBK
3419 Output 3 Unit PSI
4001 Gain 1.0
4002 Integration Time 1.0
4006 Units PSI
4010 Set Point Sel Internal
4022 Sleep Selection Internal
4024 PID Sleep Delta 10 sec
4027 PID Param Set DI3
4101 Gain 1.0
4102 Integration Time 1.0 Sec
4106 Units PSI
4109 100% value Per 4009
4110 Set Point Sel Internal
4111 Internal Setpoint Per 4011
4122 Sleep Selection Internal
4123 PID Sleep Level Per 4023
4124 PID Sleep Delay 10 sec
4125 Wake-Up Deviation Per 4025
9.6 Pentek
®
Assistant
Table 9-6: PPC3 Parameters Changed Relative to PID Control Defaults