Functional Safety KFD2-SH-Ex1(.T)(.OP), KHA6-SH-Ex1
Planning
2017-04
15
KFD2-SH-Ex1.T(.OP)
The characteristic safety values like PFD, PFH, SFF, HFT and T
1
 are taken from 
the FMEDA report and the assessment documentation created by the issuer. 
Please note, PFD and T
1
 are related to each other. The function of the devices 
has to be checked within the proof test interval (T
1
).
The safety values MTTF
d
, DC
d
, Category and PL for the machinery directive are 
taken from the assessment report and certificate.
Parameters acc. to IEC 61508 Characteristic values
Assessment type and 
documentation
FMEDA, proven-in-use assessment, certificate
Device type A
Mode of operation Low Demand Mode or High Demand Mode
HFT 0
SIL 3 (proven-in-use) 2 (proven-in-use)
Safety function Output I is de-energized when 
input in low state
Output II is de-energized when 
input in low state
s
181 FIT 194 FIT
du
1.4 FIT 51.6 FIT
dd
38.4 FIT 38.4 FIT
no effect
1
1
"Annunciation failures" are not directly influencing the safety functions and are therefore added to the 
no effect
 value.
195 FIT 130 FIT
total (safety function)
218 FIT 282 FIT
SFF 99.4 % 81 %
MTBF 
2
2
acc. to SN29500. This value is calculated with the failure rates of the device components which are part of the 
safety function of the device.
275 years 276 years
MTTF
d
2860 years –
DC
d
96.5 % (medium) –
B10
d
– –
Category (ISO 13849-1) 3 –
PL d –
PFH 1.38 x 10
-9
 1/h 5.16 x 10
-8
 1/h
PFD
avg
 for T
1
 = 1 year 6.04 x 10
-6
2.26 x 10
-4
PFD
avg
 for T
1
 = 2 years 1.21 x 10
-6
4.52 x 10
-4
PFD
avg
 for T
1
 = 5 years 3.02 x 10
-5
1.13 x 10
-3
Reaction time 
3
3
Time between fault detection and fault reaction.
< 30 ms < 30 ms
Table 3.3