Functional Safety KFD2-SR2-Ex*.W(.LB)
Planning
2020-05
11
3.2 Assumptions
The following assumptions have been made during the FMEDA:
Failure rates are constant, wear is not considered.
Failure rate based on the Siemens standard SN 29500.
The safety-related device is considered to be of type A device with a hardware
fault tolerance of 0.
External power supply failure rates are not included.
Only one input and one output are part of the safety function (only for 2-channel version).
Short circuit (SC) detection and lead breakage (LB) detection are enabled.
The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
SIL 2 application
To build a SIL safety loop for the defined SIL, it is assumed as an example that this device
uses 10 % of the available budget for PFD
avg
/PFH.
For a SIL 2 application operating in low demand mode the total PFD
avg
value
of the SIF (Safety Instrumented Function) should be smaller than 10
-2
,
hence the maximum allowable PFD
avg
value would then be 10
-3
.
For a SIL 2 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10
-6
per hour, hence the maximum allowable PFH value
would then be 10
-7
per hour.
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 60 % according to table 2 of IEC/EN 61508-2 for a SIL 2 (sub) system.
SILCL and PL Application
The device was qualified for use in safety functions up to SIL2 acc. to IEC/EN 61508.
The risk reduction is equivalent to PL d acc. to EN/ISO 13849-1 or to SILCL2 acc. to
IEC/EN 62061. See chapter 4 of EN/ISO 13849-1 for details on comparison between
SIL and PL statements.