PROBLEM CAUSE SOLUTION
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge per
Section 7.13 and 7.14.
This is a critically charged system,
recharging should only be done when
all other options have been thoroughly
checked.
Dixell Control: LED
Controller display is ash
-
ing “LA. Minimum tem-
perature alarm.
Internal compartment has exceeded the
low temperature alarm preset value for over
30 minutes.
Incorrect control settings.
Return to factory settings.
See
Section 8.6.
Probe failure.
Table 8-21 for resistance values.
Return to Table of Contents
Residential Refrigeration
and Front Venting Commercial Refrigeration
Service Manual
Troubleshooting Guide – Beverage Dispensing Page 3-8

Table of Contents