7.Troubleshooting
Problem Cause Remedy
Thedisplayshowsirrigationin
progress,butthevalvedoesnot
open.
1.Novoltageonthevalve
coil.
‐Checkcabling.
‐Measurecoilvoltage.
2.Faultyvalvecoil. Replacecoil.
3.Nowaterpressure. Checkpumpandpumprelay.
4.Novoltageatthevalve
output.
Replaceoutputmodule.
Irrigationisswitchedoff,butthe
valveisopen.TheLEDofthe
activestationisoff.
1.Voltageonthecoil.
Faultyexpansionmodule.
Replaceoutputmodule.
2.Novoltageonthecoil.
Valvemechanicallydamaged.
Checkvalve.
Displayedtimeanddayisnot
correct.
Longtermpoweroutage. Settimeandday.
Screendisplays(check)
Shortcircuitedoroverloaded
output.
Removetheshortcircuit.Unplug
controllerfromthemainstoresetit.
Automaticirrigationdoesnot
start.
1.Controllerisnotsetto
AUTOmode
TurndialtoAUTO
2.Incorrectstarttime. Setacorrectstarttime.
3.Noparticulardayhasbeen
setinthisprogram.
Setwateringdays.
Thedisplayisblank.
1.Unitisdisconnectedfrom
themains,powercut.
Checkthemainsparameters:
230V/50Hz.
2.Fuseblown.
Replacefuse.
Forthetypeseetheprintedcircuit
board(T200mA250V).
3.Defectivemotherboard. Replacethecontroller.
Nosignalisdetectedfromthe
sensor
Sensornotconnected
correctly
Checkwiring(seewiringscheme
page7)
Stationorsensornot
activated
Activatestation
Distancebetweensensorand
switchingcamistoobig
Checkdistance.Tryholdingametal
pieceinfrontofthesensortocheckif
signalisdetected
TheyellowLEDatthesensoralso
showsthissignal
VP3SCsprinklerdoesnotgointo
parkingposition
Stationnotcalibrated Calibratestationonceagain
Stationsettinghasbeen
changedmanually
Calibratestationonceagain
VP3SCdoesnotpopdownat
sectorstop
Afterruntimenotwell
adjusted
Optimizeafterruntime