EasyManua.ls Logo

Phoenix Controls PCM Series - Applications

Phoenix Controls PCM Series
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
©2009 Phoenix Controls. Specifications subject to change without notice. Rev. 11/11 MKT-0244 MPC-1673 PROGRAMMABLE CONTROL MODULE: LONMARK 3
APPLICATIONS
The Phoenix Controls PCM is a programmable input/output module that may be used as:
A standalone controller
Physical sensors and switches may be connected to the PCM, which then performs the desired control by using built-in
functions (see section below) to switch or modulate PCM outputs.
An input/output (I/O) expansion module
Physical sensors, switches and actuators may be connected to the PCM and values passed across the room-level network to a
Celeris valve controller for use in its control sequence. Data from the PCM may also be passed across the building-level network
to the BMS for monitoring purposes.
A controller integrated into the Celeris, Theris or Traccel system
Data may be passed between the valve mounted controllers and PCM on the room-level network to supplement the control
functions of either device. An example might be interlocking door locks between an anteroom and a space under control so that
doors may not be opened until the pressure stabilizes or a certain number of air changes have occurred.
Outputs
Digital
1
24 Vac Triac, digital (on/off), floating
2
or PWM
0.75A @158
°
F (70
°
C)
1A @ 104
°
F (40
°
C)
PWM control: adjustable period from 2 seconds to 15 minutes
•Min. pulse on/off: 500 msec.
Adjustable drive time period
External or internal power supply (jumper selectable)
Universal Software configurable
0-10 Vdc, 0-20 mA
3
, digital 0-12 Vdc (on/off), floating or PWM
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
Min. pulse on/off: 500 msec.
Adjustable drive time period
60 mA max. @ 12 Vdc 140
°
F (60
°
C)
Minimum resistance 200
Auto-reset fuse
60 mA @140
°
F (60
°
C)
100 mA @68
°
F (20
°
C)
Output Resolution 10-bit analog/digital converter
Power Supply
15 Vdc; maximum 240 mA
3
DC Relay Kit
Relay Coil Characteristics:
Rated voltage: 12 Vdc
Rated current: 33.3 mA
Resistance: 360
Minimum operating voltage: 8.4 V
Operating Temperature: -40
o
F to 185
o
F (-40
o
C to 85
o
C)
Storage Temperature: -40
o
F to 221
o
F (-40
o
C to 105
o
C)
Agency Approvals: VDE, RU, CSA, RoHS
Contact Characteristics:
Maximum power rating: 2500 VA
Rated current: 10A
Rated voltage: 250 Vac
Standard contact material: Silver-nickel 90/10
Type of Duty: Continuous
Mechanical life expectancy: 1x10
6
operations
Weight: 10 grams
Dimensions (L x W x H): 3.0" x .62" x 2.42" (76.2 mm x 15.8 mm x 61.5 mm)
1
PCM200 and PCM201 only.
2
Floating control: requires two consecutive outputs.
3
PCM203 only.