©2009 Phoenix Controls. Specifications subject to change without notice. Rev. 11/11 MKT-0244 MPC-1673 PROGRAMMABLE CONTROL MODULE: LONMARK 9
PHOENIX RECOMMENDED CABLES
Cable
Type
Plenum
Rated
Function
Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part#
Color Code Notes
2C
Round
No 24 Vac power
(110’ max)
18 Belden 9409 1: Red
2: Black
Must be
stranded
14
1
Belden 9411
3C
Round
No ± 15 Vdc power 22 Belden 8443 1: Red
2: Black
3: Green
Must be
stranded
2C
Round
Yes 24 Vac power
(110’ max)
18 Belden 82740 Windy City
NP002 360
1: Red
2: Black
Must be
stranded
14 Windy City
NP007 960
3C
Round
Yes ± 15 Vdc power 22 Belden 88444 Windy City 004380 1: Red
2: Black
3: Green
4: White (N/A)
Must be
stranded
TP No FTT-10 (4500’)
TP1250 (425’)
22 Windy City 107500 BICC Gen C8641
Eastman Wire
LEV4221
1: White/Blue
stripe
2: Blue/White
stripe
For more
alternatives
visit:
echalon.com
FTT-10 (8800’) 16 Windy City 109600 BICC Gen C8661
Eastman Wire 5705
TP Yes FTT-10 (4500’)
TP1250 (425’)
22 Windy City 105500 BICC Gen. 8601
Eastman Wire
LEV4221P725
1: White/Blue
stripe
2: Blue/White
stripe
For more
alternatives
visit:
echelon.com
FTT-10 (8800’) 16 Windy City 109500 BICC Gen. C8621
Eastman Wire
725-5705
TSP No I/O signal wiring 22 Belden 9501 1: Black&Red Twisted
Shielded Pair
2 TSP No I/O signal wiring 22 Belden 9502 1: Black&Red
2: Black&White
Two Twisted
Pair,
Shielded
3 TSP No I/O signal wiring 22 Belden 9503 1: Black&Red
2: Black&White
3: Black&Green
Three
Twisted Pair
Shielded
8C
Shield
No I/O fume hood
controls,
Thermostats
22 Belden 9944 1: White (N/A)
2: Orange
3: Black (N/A)
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
8 Conductor,
Shielded
8C
Shield
Yes I/O fume hood
controls,
Thermostats
22 Windy City 004352 1: White (N/A)
2: Orange
3: Black (N/A)
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
8 Conductor,
Shielded
1