Description of Function Codes PE6000 User Manual
128
state is 50.00 x 2.000 = 100.00 (display of 2 decimal places).
Function
Code
Parameter Name Setting Range Default
P7-13 Accumulative power-on time 0–65535 h 0h
It is used to display the accumulative power-on time of the AC drive since the delivery. If the
time reaches the set power-on time (P8-17), the terminal with the digital output function 24
becomes ON.
Function
Code
Parameter Name Setting Range Default
P7-14 Accumulative power consumption 0–65535 kWh /
It is used to display the accumulative power consumption of the AC drive until now.
Group P8: Auxiliary Functions
P8-00
JOG running frequency Default 6.00Hz
Setting Range 0.00 Hz to maximum frequency
P8-01
JOG acceleration time Default 20.0s
Setting Range 0.0–6500.0s
P8-02
JOG deceleration time Default 20.0s
Setting Range 0.0–6500.0s
These parameters are used to define the set frequency and acceleration/deceleration time of
the AC drive when jogging.
The startup mode is "Direct start" (P6-00 = 0) and the stop mode is "Decelerate to stop" (P6-10
= 0) during jogging.
P8-03
Acceleration time 2 Default 20.0s
Setting Range 0.00 Hz to maximum frequency
P8-04
Acceleration time 2 Default 20.0s
Setting Range 0.0–6500.0s
P8-05
Acceleration time 3 Default 20.0s
Setting Range 0.0–6500.0s
P8-06
Acceleration time 3 Default 20.0s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pioneer PE6000-3T18.5GB and is the answer not in the manual?

Pioneer PE6000-3T18.5GB Specifications

General IconGeneral
BrandPioneer
ModelPE6000-3T18.5GB
CategoryDC Drives
LanguageEnglish

Related product manuals