PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
5
1.0 The PDRP-1001/PDRP-1001A
1.1 Features
• Microprocessor-controlled
• Alarm and trouble resound
• Four Style B/D Initiating Device Circuits
• Two Style Y/Z Notification Appliance Circuits
• Two Style Y Release Circuits
• General alarm and trouble relays
• Optional module for 4 zone/function relays (4XZM)
• Optional transmitter module (4XTM). Complies with
NFPA 72 Auxiliary and Remote Station Fire Alarm
Systems.
• Optional volt/amp meter module (4XMM)
• Optional supervised remote annunciator
(RZA-4X). Requires LED Interface Module (4XLM)
• Optional digital communicator (NOTI•FIRE 911AC).*
• Complies with NFPA 72 Central Station and NFPA 72
Remote Station Fire Alarm Systems.
• Designed for sprinkler standards NFPA 13, 15, and 16.
• Disable/enable controls per initiating zone.
• Last Event Recall
• Battery/Earth fault supervision
• Fuse protection on all Notification/Release Circuits
• RMS regulated output power, 2.25 amps
• 7 amp/hour to 15 amp/hour battery options,
up to 90 hours standby
• Resettable and non-resettable regulated
power outputs
• Extensive transient protection
• Watchdog timer to supervise microproces-
sor (includes MICRO FAIL LED)
• Output circuits protected against false
activations.
• Slide-in zone identification labels
• Steel cabinet 14.5" wide by 16" high by 5"
deep
• Dead-front dress panel option (DP-4X)
• Trim ring for flush mount between 16" center
studs (TR-4XR)
• Cross-zone (double-interlock) option
• Municipal Box output.
• Interface Module (4XLM)
• Dual hazard operation
• Adjustable discharge timer
* Applications which require the NOTI-FIRE 911AC is not FM approved.
1.2 Circuits
Input Circuits
Manual Release/Detector Circuit 1 (Style B/D)
Detector Circuit 2 (Style B/D)
Waterflow (Style B/D)
Supervisory (Style B/D)
Output circuits (optional auxiliary relay module (4XZM) tracks these four circuits)
Alarm/Waterflow Bell (Style Y/Z)
Waterflow/Supervisory Bell (Style Y/Z)
Releasing Circuit 1 (Style Y)
Supervisory Bell/Release Circuit 2 (Style Y)
Front Panel Control Switches
Switch 1 Tone Silence
Switch 2 Alarm Silence
Switch 3 Alarm Activate
Switch 4 System Reset