EasyManua.ls Logo

Pittway System Sensor PDRP-1001 - Remote Annunciator; Optional Meters

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
8
LED Interface Module (4XLM NOTIFIER)
Maximum voltage/current, each output: 27.6V/8mA.
Note: Outputs are power limited.
Zone Relay Module (4XZM NOTIFIER)
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
1.4 Remote Annunciator
Remote Annunciator (RZA-4X NOTIFIER)
The Remote Annunciator mounts on a standard single-gang box, and provides LED
indication of the following:
Alarm/Waterflow Bell (red)
Waterflow/Supervisory Bell (red)
Releasing Circuit 1 (red)
Supervisory Bell/Release Circuit 2 (red)
System Trouble LED (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is
supervised for open conditions. Any open condition will cause the System Trouble
LED to illuminate.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
1.5 Optional Meters
Voltage, Current Meters (4XMM NOTIFIER)
The Meter Module provides a voltmeter to measure the voltage across the
batteries and an ammeter to measure the charging current to the batteries. The
meters are provided as a assembly that mounts to the lower left corner of the
cabinet.
Transmitter Module (4XTM NOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
For Remote Station service (NFPA 72 Remote Station Fire Alarm System):
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.