Installation of intrinsically safe circuits must fulfill requirements of standard EN 60079-25:2010.
Grounding of the interface - terminal no. 3 connect to earth bar, terminal no. 9 connect to earth grounding.
Ex cables must be passed separately to non-Ex cables. Wiring must meet EN 60079-14 ch. 12.2.2.8.
Wires and cables of Ex circuits should be rigidly placed and secured from mechanical factors.
LIYCY type cables for intrinsically safe circuits are highly recommended, option for blue insulation.
Permissible cable lengths: RS485 Ex – 150m for LIYCY 6x0,5mm² or 100m for LIYCY 6x0,34mm².
Shielding of RS485 Ex cable connect to SHIELD terminal and earth grounding. Avoid grounding loops.
For longer than 30 meters, ground shield cable using surge protection device, not in explosive zone.
Do not install the interface in vicinity of strong electrical or magnetic fields.
Device Ex marking is II (2)G [Ex ib Gb] IIA. Housing protection class is IP40.
Input voltage range 10.5-30V DC. Output voltage is ~5.7V (INT-S3) or ~7.6V (INT-S3/N).
Supports RS485 Ex and RS485. Baud rate 9600-115200b/s. Intrinsically safe circuits Z1, Z2; standard circuits Z3, Z4.
Assembled on DIN rail (TS35). Outputs are OC type, max load up to 200mA.
INT-S3 is for power supply (5.7V) in Ex zone, or Ex barrier for RS485 and Digital Outputs.
INT-S3/N is for power supply (7.6V) in Ex zone, or Ex barrier for RS485 and Digital Outputs.
INT-S3/N cannot be main power supply for MacBAT 5/MacREJ 5; only as Ex barrier for RS485/Digital Outputs.
Diagram shows INT-S3 connection with MacBAT 5 / MacREJ 5, including RS485 Ex and RS485 ports.