MODBUS RTU Instruction Manual - 2017-11-02.docx Page 10 of 14 November 2, 2017
Table #1
Bit
Pos.
Status
Wired S
stems Wireless S
stems
DB0 Deliver
in Pro
ress
LSB
DB1 Probe S
nc Erro
Probe Level Erro
DB2 Probe Timeout Erro
DB3 In-Tank Leak Test in Pro
ress N/
DB4 Pump/Generator Run
DB5 Ulla
e Mode LSB
See table below
DB6 Ulla
e Mode MSB
See table below
DB7 In-Tank Product Motion
Note: Active LOW
DB8 No Monthl
Leak Test Warnin
N/
DB9 Product Below Gau
eable Level
DB10 Theft Alarm
DB11 Water Setpoint Alarm
HIGH
DB12 Product Setpoint Alarm #3*/
LOW
**
DB13 Product Setpoint Alarm #2*/
HIGH
**
DB14 Product Setpoint Alarm #1*/
HIGH HIGH
**
DB15 In-Tank Leak Alarm
MSB
N/
DB16 N/
WiS Erro
DB17 N/
WiDAM Timeout Erro
DB18 N/
WiDAM Low Batter
Warnin
DB19 N/
Probe Temperature Erro
DB20-
31
Spare (All zeros)
ll statuses Active HIGH unless otherwise noted
*Product Setpoint Alarms are programmable for both magnitude and direction.
Factory defaults are as follows, but actual TMS settings should be confirmed;
Product Setpoint #1 95% High High
Product Setpoint #2 90% High
Product Setpoint #3 20% Low
Ullage % Ullage Mode MSB Ullage Mode LSB
85 1 1
90 0 0
95 0 1
100 1 0