MODBUS RTU Instruction Manual - 2017-11-02.docx Page 13 of 14 November 2, 2017
2.1.4 Contact Closure Data Register - CC Number Detail
Re
g
ister
DB15-12 DB11-8 DB7-4 DB3-0
40204 4 3 2 1
40205 8 7 6 5
40206 12 11 10 9
40207 16 15 14 13
2.1.4.1 Contact Closure Data Register - Status Detail
Status MSB 3SB 2SB LSB
Not Active 0 0 0 0
A
ctive, Rela
y
Control 0 0 0 1
A
ctive, Gate Control 0 0 1 0
A
ctive Alarm 0 0 1 1
A
ctive Acknowled
g
e 0 100
Not Enabled 1 1 1 1