Perioada 1 2 3 4
Ora Temp Ora Temp Ora Temp Ora Temp
12345 (Luni-Vin) 7:00 22
o
C 8:30 19
o
C 17:00 22
o
C 22:00 19
o
C
6 (Sambata) 8:00 22
o
C 8:30 22
o
C 17:00 22
o
C 22:00 19
o
C
7 (Duminica) 8:00 22
o
C 8:30 22
o
C 17:00 22
o
C 22:00 19
o
C
SETARI AVANSATE PARAMETRI
Opriti termostatul apasand butonul On/Off ( Pornit/Oprit) . Cu ecranul stins apasati simultan butoanele
si pentru setare avansata parametri.
MENIU Descriere Plaja valori Valoare implicita
01 Calibrare temperatura senzor intern -8
o
C ~ 8
o
C 0
o
C
02 Setare limita maxima temp. 5
o
C ~ 35
o
C 35
o
C
03 Setare limita minima temp. 5
o
C ~ 35
o
C 35
o
C
05 Temperatura protectie inghet 5
o
C ~ 15
o
C 5
o
C
09 Histerezis (Deadzone) 0
o
C ~ 3
o
C 0
o
C
12 Functie detectie geam deschis-OWD 1: Pornit 0: Oprit 0
13 OWD - Timp detectie 2 ~ 30 minute 15 minute
14 OWD - Scadere temperatura
( in timpul de detectie)
2,3,4
o
C 2
o
C
15 OWD - Timp Intarziere
( revenire la setare/program anterior)
10 ~ 60 minute 30 minute
17 Revenire la setarile din fabrica 0 : Nu 0
1: Da, si apasati Butonul
On/Off ( Pornit Oprit) timp
de 5 secunde pana se
restarteaza termostatul.
Versiune Software 5055-02
DIAGRAMA CONEXIUNI UNITATE RECEPTOR
Operatiunea de conectare a unitatii receptor la o sursa de alimentare 230V , si la o centrala termica
se executa doar de catre personal calicat, si doar dupa ce se consulta in prealabil documentatiile
termostatului, si ale centralei termice.
Unitatea receptor are o comanda de tip releu ( NO si NC / Normal Deschis si Normal Inchis) ce suporta
inchiderea unui circuit de comanda cu un curent maxim de 10 A.