EasyManua.ls Logo

Potter PAD200-DUCT - Page 2

Potter PAD200-DUCT
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION MANUAL: PAD200-DUCT ANALOG ADDRESSABLE DUCT DETECTOR
Document 5406428-A 02/21
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 2 OF 4
The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device not addressed where all
dip switch settings are in the default "O" position, the 2nd illustrates an addressed PAD device via the dip switch settings.
Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.
• Power to the SLC is removed.
• Field wiring on module is correctly installed.
• Field wiring has no open or short circuits.
3. Technical Specications
Duct Detector Model # PAD200-DUCT
Operating Voltage 24.0V
Current Draw 300μA
Detector Head Model PAD200-DD
Detector Head Type Photoelectric
Sensitivity Test Method Self diagnostic test
Air Velocity 100 to 4000 ft./min.
Ambient Temperature
32to 120F (0to 49C)
Humidity 10% to 85% Relative humidity (non-condensing)
Housing Material Plastic backbox, clear plastic cover
Finish Gray backbox with clear cover
Dimensions 13 1/2" L x 4 1/2" W x 2 1/4" D
Maximum Net Weight 2 lbs.
Sampling Tubes 2.5 ft., 5 ft., or 10 ft.
Sampling Tube Part Numbers 2.5' = 1000274, 5' = 1000275, 10' = 1000276
4. Wiring Diagram
The wiring diagram shown below illustrates how to wire a PAD200-DUCT duct detector.
Figure 3. Example of Wiring a PAD200-DUCT Duct Detector
Notes:
• SLC wiring style supports the Class A, Class X and Class B.
• SLC loop wiring is power limited.
• SLC loop wiring is supervised.
• Wiring for terminals are supervised.
• All wiring is between #12 (max.) and #22 (min.).
• Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
– Stripping too much insulation may cause a ground fault.
– Stripping too little may cause a poor connection and subsequently an open circuit.
1/4 inch
+SLC
-SLC
-SLC
FROM FACP or
PREVIOUS MODULE
TO NEXT MODULE
+SLC
Off
On
1 2 4 16
8 32 64
All dip switches are
shown in the "O󰀨"
position.
Off
On
1 2 4 16
8
32 64
Example shows this PAD device's
address = 42. Dip switches #2, 8 &
32 are in the "On" position.