SAVE THESE DOCUMENT IN A SAFE PLACE!
IMPORTANT SAFETY INSTRUCTIONS!
This manual contains important safety instruction that must be followed during the installation and start-
up of the device. It’s recommended to give special attention to the installation instruction in order to reduce
the risks of electric shock and prevent damage to the device.
This document contains proprietary information of Power-One, Inc. The contents of this document or anypart
thereof should not be reproduced or disclosed to any third party whitout Power-One’s express written consent.
Any changes /modication not approved by the responsible party could void the user authority to operate
the equipment.
BCM.00101.3 07-02-2013REV. 3.2
PHOTOVOLTAIC INVERTER
INSTALLATION AND CONFIGURATION MANUAL

Questions and Answers

  • G
    gwhiteAug 15, 2025
    What to do if my Power One Aurora PVI-5000-TL-OUTD Inverter does not establish parallel with the grid?
    • L
      Lisa EdwardsAug 15, 2025
      If your Power One Inverter isn't establishing a parallel connection with the grid, it might be due to the absence of grid voltage. First, check the status of the AC side disconnecting switch. Then, verify the inverter's AC side connections, and repeat the commissioning procedure.
  • C
    Carly MaxwellAug 18, 2025
    Why my Power One Inverter does not start?
    • N
      Nicholas LewisAug 18, 2025
      The Power One Inverter might fail to start due to the absence of input DC voltage or if the polarity is reversed. To resolve this: * Check the status of the built-in or external disconnecting switches. * Inspect any internal or external fuses. * Verify the inverter's input voltage polarity. * Ensure the input voltage exceeds 120V (refer to the technical data).
  • J
    Jonathan MorrisAug 22, 2025
    What to do if Power One Aurora PVI-5000-TL-OUTD shows 'W003 Grid Fail'?
    • A
      Anthony StoneAug 22, 2025
      If your Power One Inverter displays 'W003 Grid Fail' and doesn't establish parallel with the grid, it could be due to a faulty grid cable connection or grid parameters being outside the permitted range. Check the inverter's AC side connections and repeat the commissioning procedure. Also, verify that the grid voltage measured on the AC terminal block falls within the acceptable amplitude and frequency ranges for the inverter's operation. If the error persists, consider contacting Power- One support.
  • S
    Stacey GatesAug 26, 2025
    What to do if Power One Inverter displays 'Missing Grid'?
    • J
      jennifer10Aug 26, 2025
      If your Power One Inverter displays 'Missing Grid', it means there is no grid voltage. Check the status of the AC side disconnecting switch and the inverter’s AC side connections, then repeat the commissioning procedure.
  • M
    Melissa GomezAug 29, 2025
    What does 'E025 Riso Low' mean on my Power One Inverter?
    • D
      Daniel PerkinsAug 29, 2025
      If your Power One Inverter displays 'E025 Riso Low', it indicates that the insulation resistance to the photovoltaic field is less than 1 Mohm. Check the inverter’s AC side connections and repeat the commissioning procedure. Also, check the appropriateness and the conditions of the external transient overvoltage protection devices. If the check is passed, yet the problem persists, remove the external transient overvoltage protection devices and repeat the commissioning procedure.
  • C
    Chad EvansAug 31, 2025
    How to troubleshoot a Power One Inverter that does not start?
    • A
      Alice JimenezAug 31, 2025
      If your Power One Inverter doesn't start, it could be due to a lack of input voltage (DC) or reversed polarity. To resolve this, check the built-in or external disconnecting switches, inspect any internal or external fuses, verify the inverter's input voltage polarity, and ensure the input voltage exceeds the inverter's start-up voltage.
  • S
    Susan MuellerSep 4, 2025
    Why is my Power One Inverter showing 'Waiting Sun'?
    • J
      Jonathan WelchSep 4, 2025
      If your Power One Inverter displays 'Waiting Sun' and fails to establish parallel with the grid, the inverter's input voltage might be lower than the required start-up voltage. Ensure the input voltage exceeds the start-up voltage and that there's sufficient radiation for system operation. Also, inspect the inverter's DC side and string connections. You may also need to review the photovoltaic system's sizing documentation and consider adjusting the start-up voltage on the display.
  • J
    jessica98Sep 7, 2025
    What does 'E013 Wrong Mode' mean on Power One Aurora PVI-5000-TL-OUTD Inverter?
    • M
      Marvin HernandezSep 8, 2025
      If your Power One Inverter displays 'E013 Wrong Mode', it is due to an incorrect configuration of the input channels. Specifically, the operation mode selection switch of the input channels is set to PAR (channels in parallel), but the inputs of the inverter are not short-circuited (independent channels). Check the status of selection switch for the input channel operating mode and for jumpers between the input channels.
  • M
    Mark MorrisonSep 12, 2025
    Why Power One Inverter shows 'W003 Grid Fail' due to high grid voltage?
    • M
      Melanie JenkinsSep 12, 2025
      If your Power One Inverter displays 'W003 Grid Fail', it means that the grid voltage exceeds the maximum value allowed for grid connection. Reduce the power of the photovoltaic generator by disconnecting strings or creating shading. If the issue persists and you notice an increase in grid voltage, it indicates high line impedance.

Summary

General Safety and Information

Important Safety Instructions

Key safety warnings and procedures for safe operation.

Safety and Regulatory Information

General Safety Regulations

Mandatory safety compliance and operational rules for qualified staff.

Installation Location and Mounting

Wall Mounting Procedure

Step-by-step guide for securely mounting the inverter onto a wall.

Electrical Connections

General Connection Warnings

Critical warnings regarding transformer-less design, grounding, and tampering.

AC Side Connection Procedure

AC Terminal Block Connections

DC Side Connection Procedure

Input Channel Configuration

Parallel Mode Setup

Pre-Commissioning Checks

Electrical Checks

Essential electrical checks before commissioning the inverter.

Commissioning and Grid Setup

Grid Standard Selection

Selecting the correct grid standard for regional compliance.

Grid Connection Procedure

System Configuration

Start-up Troubleshooting

Common Issues and Solutions

Troubleshooting common problems encountered during the inverter's initial start-up phase.

Special Maintenance

Troubleshooting Assistance

Power One Aurora PVI-5000-TL-OUTD Specifications

General IconGeneral
ManufacturerPower One
ModelAurora PVI-5000-TL-OUTD
Rated Power5000 W
Max. DC Power5500 W
Max. DC Voltage900 V
Number of MPPT2
AC Voltage230 V
MPPT Range250 - 800 V
AC Output Voltage230 V
Frequency50/60 Hz
Protection DegreeIP65
Operating Temperature Range-25 °C to +60 °C
Cooling MethodNatural convection
Weight25 kg
Input Voltage Range200 V - 800 V