SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
Engine does not crank Loose battery cables Check all battery cable connections
Defective battery Test battery. Replace as necessary.
Check battery charger inline fuse
Improper battery charger function
Ensure charger is plugged into GFCI
receptacle
Check for tripped GFCI receptacle. Reset if
required.
Check for tripped breaker in branch circuit
supplying GFCI. Reset if required.
Check all charger cable connections for
cleanness and tightness.
Check charger lights to verify correct
operation. See Table A, Page 29.
Fault in starter signal circuit
Contact a qualified generator dealer for service
assistance.
Blown control circuit fuse Check control circuit fuse.
Engine cranks without starting Low battery Test battery. Replace as necessary.
Ensure charger is plugged into GFCI
receptacle
Check for tripped GFCI receptacle. Reset if
required.
Check for tripped breaker in branch circuit
supplying GFCI. Reset if required.
Check all charger cable connections for
cleanness and tightness.
Check charger lights to verify correct
operation. See Table A, Page 29.
Poor fuel supply Ensure all manual shutoff valves are open
Check for proper fuel supply pressure
Verify size and fill level of propane tank (LPG
only)
Check fuel solenoid voltage during cranking
Low oil pressure Check engine oil level
Check switch for proper function
High engine temperature Allow engine to cool, then restart
Decrease loads on generator
Check enclosure openings for blockage
Check oil cooler for blockage
No generator output Main line circuit breaker tripped
Check breaker. Clear faults, then reclose
breaker.
Disconnect breaker tripped
Check for tripped breaker in circuit between
generator output and transfer switch. Clear
fault, then reclose breaker.
Generator loss of excitation
Contact a qualified generator dealer for service
assistance.
Excitation capacitor failure
Contact a qualified generator dealer for service
assistance.
Generator diode or varistor failure
Contact a qualified generator dealer for service
assistance.
Generator head fault
Contact a qualified generator dealer for service
assistance.
Engine starts then
immediately shuts down