Section V Control panel and operation
16
Protection is higher than the set
value.
0 limit current; 1 voltage; 2 jump;
limit current; 3 jump + voltage; 4
current ramp; 5 double closed loop; 6
monitoring.
0 primary; 1 light load; 2 standard; 3
heavy load; 4 advanced.
0 keyboard; 1 keyboard + external
control; 2 external control; 3 external
control + communication; 4
keyboard + external control +
communication; 5 keyboard +
communication; 6 communication.
Parameter
modification
allowed
See 5.5 other setup instructions.
For MODBUS native slave address
setting.
See 5.3 programmable relay output
functions.
See 7.3.1 soft stop mode.
Nominal rated current for input
motor.
Used to set bypass time delay.
0 is prohibited, 1 is allowed.
Used to adjust the current value of
the display.
Used to adjust the display voltage
value.
Note: 1, set the P6 load adjustment rate is calculated based on the load weight of the
motor in the number of PP based on the calculation of the maximum current, more than
this value will do the inverse time thermal protection.
2, setting the state, if more than 2 minutes without a button operation, will
automatically exit the setting state.
3, in the soft start and soft stop process can not set parameters, the other state can be set
parameters.
4, according to the confirmation key (PRG) on the power on the boot, can set
parameters to restore the factory value.
5-3 Programmable relay output functions
There are two programmable relay output function, programmable timing output
way and programmable state output way.
5-3-1. PE set from 0 to 4 items (10 ~ 14), programmable output work is timing
output way, the setting of output starting time as tabled below.