13
OP2 Function : Blower / Compressor Control
Parameter Description
Settings
Default Value
OFFSET VALUE
Sets a positive (+) offset to the SP to define the ‘Blower /
Compressor Setpoint’.
Blower / Compressor Setpoint = Control Setpoint (SP) + Offset
Value
0 to 250 or
0.0 to 25.0
(Default : 0)
HYSTERESIS
Differential (dead) band between the blower ON and OFF states.
1 to 250 or
0.1 to 25.0
(Default : 2 or 0.2)
TIME DELAY
This parameter is mainly used for Compressor Load. The set time
delay is elapsed each time before the compressor is switched ON.
Set the value to 0 if no Time Delay is required.
00.00 to 10.00 Min. Sec
(in steps of 5 Seconds)
(Default : 00.00)