EasyManua.ls Logo

PPI Zenex - Temperature Sensor Input Connections (96 x96); Output-1 Control Output Connections (96 x96)

PPI Zenex
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
OUTPUT-1 (Control Output)
The Output-1 is factory configured as either Relay / SSR Drive or DC Linear mA / V.
Note that Relay / SSR outputs are simultaneously provided on separate terminals. Refer Figure 3.3 (a).
For DC Linear mA/V, use terminals 4 & 6 as shown in Figure 3.3 (b).
Figure 3.3 (a) Figure 3.3 (b)
6
5
4
11
10
6
5
4
NO
C
NC
Relay Output
SSR Output mA/V Output
Relay Output
Potential-free Relay changeover contacts NO (Normally Open) and C (Common) rated 10A/240 VAC (resistive load).
SSR Output
Connect (+) and (-) terminals of SSR to terminals 11 & 10, respectively. Use Zero-Crossover, 3 to 30 VDC operated SSR.
mA / V Output
The Positive (+) of mA / V is available at Terminal 6 & the Negative (-) at Terminal 4.
OUTPUT- 2 (Alarm / Blower / Auxiliary Control)
OUTPUT- 3 (Alarm / Auxiliary Control)
The numbers in brackets indicates the terminal numbers for Output-3.
User Manual
TEMPERATURE SENSOR INPUT
Connect Thermocouple or 3-wire RTD Pt100 sensor as shown below.
3
2
1
Figure 3.2 (a)
Thermocouple
3
2
1
Figure 3.2 (b)
RTD
Thermocouple
Connect Thermocouple Positive (+) to terminal 1 and Negative (-) to terminal 2 as shown in Figure 3.2 (a). Use correct type of
extension lead wires or compensating cable. Avoid joints in the cable.
RTD Pt100, 3-wire
Connect single leaded end of RTD bulb to terminal 1 and the double leaded ends to terminal 2 and 3 (interchangeable) as
shown in Figure 3.2 (b). Use low resistance copper conductor leads of the same gauge and length. Avoid joints in the cable.
zenex96

Related product manuals