2224V103-UK 13
Configuration / operating the function keys
Documentation for routing diagram
General
The configuration is menu-controlled. The main menus are numbered in level 0 (x.0), and the submenus are numbered in level
1 (x.1 to x.4). Each submenu has an accompanying entry menu. The menus are structured in such a way that the menus most
frequently used are closer to the default menu 0.0. Please note that programming is only possible when submenu 1.1 PAS has
the value 030.
All changes are not permanently saved in the EEP rom, until you return to menu 0.0.
Menus and submenus are selected by the 3 function keys 3, 1, and 2 as outlined
in the routing diagram.
Activating 2 in the submenu will display the current value in the entry menu.
In entry menus, the digit that can be changed will flash.
Active digit position is shifted by the 3 key, and the value is changed by the 1
key.
In parameter selection menus you switch between the parameters by using the
1 key.
To store changes temporarily press 31 simultaneously.
To store changes permanently go to menu 0,0.
To return to the previous menu without changing the parameters - press 2.
0.0. Default - Output percentage value of I
valve
is displayed
At power ON, or if no keys have been activated for a period of 2 minutes, the display returns to default.
1.0 VAL - Enter password
1.1 PAS - Programming access
Accepted password is valid until power off.
The password is 030.
2.0 CUA - Setting of currents for A valve
2.1 LOA - Spring response for A valve
The parameter is entered as a percentage of the Ivalve.
Valid selections are 0...99.9%.
2.2 IA1 - Current limit Imax1
The parameter is entered as a percentage of the Ivalve.
Valid selections are 0...99.9%.
2.3 IA2 - Current limit Imax2
The parameter is entered as a percentage of the Ivalve.
Valid selections are 0...99.9%.
3.0 CUB - Setting of currents for B valve
Please see the setup of the A valve (2.0 CUA).
1.0 1.1
Memory
Programming
Change of parameter
Next digit or point
Go to entry menu / Leave
menu without changes
To store changes press
simultaneously.

Other manuals for PR electronics 2224

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PR electronics 2224 and is the answer not in the manual?

PR electronics 2224 Specifications

General IconGeneral
BrandPR electronics
Model2224
CategoryController
LanguageEnglish