8 2284V104-UK
Relative air humidity .............................................. < 95% RH (non-cond.)
Dimensions (HxWxD) (D is without pins) ....... 80.5 x 35.5 x 84.5 mm
Protection degree .................................................... IP50
Weight DC / universally supplied ...................... 125 g / 165 g
Input:
Measurement range ................................................ -50...+50 mADC
Min. measurement range (span) ........................ 0.53 mADC
Max. offset ................................................................. 50% of max. value
Input resistance........................................................ Nom. 50 Ω
Voltage:
Measurement range ................................................ -250...+250 VDC
Min. measurement range (span) ........................ 27 mVDC
Max. offset ................................................................. 50% of max. value
Input resistance........................................................ >1 MΩ...<10 MΩ
Current output:
Signal range ............................................................... 0...20 mA
Min. signal range ...................................................... 4 mA
Max. offset ................................................................. 20% of max. value
Load (max.) ................................................................. 20 mA / 1000 Ω / 20 VDC
Load stability ............................................................. < ±0.01% of span / 100 Ω
Current limit ............................................................... 23...28 mA
Voltage output through internal shunt:
Signal range ............................................................... 0...10 VDC
Min. signal span ........................................................ 200 mVDC
Max. offset ................................................................. 20% of max. value
Load (min.) .................................................................. 500 kΩ
Buffered voltage ...................................................... Min. 0.2...1 VDC / max. 0...20 VDC
Max. load ..................................................................... 10 mA
Observed authority requirements: Standard:
EMC 2004/108/EC .................................................. EN 61326-1
LVD 2006/95/EC ...................................................... EN 61010-1
PELV/SELV .................................................................. IEC 364-4-41 and EN 60742
EAC TR-CU 020/2011 ............................................ EN 61326-1
Of span = Of the presently selected range