10 2284V104-UK
PROGRAMMING
INPUT
PROGRAMMING
DP1 (10-pole)
SW 1, 2, 3, 4, 5, 6
JP1
POSITION
SW ON SW OFF 1 - 2 2 - 3
0...5 mA
0...20 mA
0...100 mV
0...500 mV
0...1 V
0...2.5 V
0...10 V
0...100 V
1, 2, 3
1, 2, 3, 4
-
4
3
3, 4
2
2, 4
4, 5, 6
5, 6
1, 2, 3, 4, 5, 6
1, 2, 3, 5, 6
1, 2, 4, 5, 6
1, 2, 5, 6
1, 3, 4, 5, 6
1, 3, 5, 6
X
X
X
X
X
X
X
X
For 20% oset on input,
set DP1 SW5 ON
e.g. input 4...20 mA
1, 2, 3, 4, 5
6
X
For bipolar input
set DP1,SW6 ON
e.g. -10 V...+10 V
2, 6
1, 3, 4, 5
X
OUTPUT
PROGRAMMING
DP1 (10-pole)
SW 7, 8, 9, 10
**DP2 (10-pole)
SW 1, 2, 6, 7, 8, 9, 10
SW ON SW OFF ON OFF
0...5 mA
0...20 mA
0...5 mA / 0...250 mV
0...20 mA / 0...1 V
0...5 mA / 0...2.5 V
0...20 mA / 0...10 V
8
7
8
7
8
7
7, 9, 10
8, 9, 10
7, 9, 10
8, 9, 10
7, 9, 10
8, 9, 10
6, 7
6, 8
1, 6, 7
1, 6, 8
2, 6, 7
2, 6, 8
1, 2, 8, 9, 10
1, 2, 7, 9, 10
2, 8, 9, 10
2, 7, 9, 10
1, 8, 9, 10
1, 7, 9, 10
For 20% oset on output,
set DP1 SW9 ON,
DP2 SW9 and SW10 ON
e.g. output 4...20 mA
7, 9
8, 10
6, 8, 9, 10
1, 2, 7
For reversed output
set DP1 SW10 ON
e.g. output 20...4 mA 7, 9, 10 8 6, 8, 9, 10 1, 2, 7
** DP2 SW 6 is ON and SW 3, 4, 5 are OFF, except for buffered output 2284---2.
Note: At other spans than the above-mentioned and at a buffered voltage output,
DP1, DP2, JP1, and JP2 have a different setting which applies to the delivered
special range. The buffered voltage output cannot be programmed acc. to the
above programming table, but will be delivered fully-configured from factory.