3100V106-UK 9
6 mm series of temperature and converters
3101 / 3102 / 3111 / 3112 / 3113 / 3331 / 3333 / 3337
Converts process measurements from Pt100, TC J and K temperature sensors to
voltage or current outputs
Multiple pre-calibrated temperature ranges are selectable via DIP-switches
High accuracy, better than 0.05% and excellent 50/60 Hz noise suppression
Fast signal response time < 30 ms
3113 and 3337 with HART 7 protocol and fast signal response time < 60 ms
HART 7 protocol enables extended device programming for 3113 and 3337
Applications
The temperature converters measure standard 2-, 3- or 4-wire Pt100 and/or TC J & K temperature sensors, and provides
an analog voltage or current output.
High 3 port isolation provides surge suppression and protects the control system from transients and noise.
The loop powered devices have high 2-port galvanic separation to eliminate ground loops.
The devices can be mounted in the Safe area or in Zone 2 / Division 2 areas.
Approved for marine applications.
Technical characteristics
High conversion accuracy, better than 0.05% of span.
A visible green LED indicates operational status and status of the input sensor.
All terminals are protected against overvoltage and polarity error.
Meeting the NAMUR NE21 recommendations, the system 3000 devices ensure top measurement performance in harsh
EMC environments.
The devices meet the NAMUR NE43 standard defining out of range and sensor error output values.
High galvanic isolation of 2.5 kVAC.
Excellent signal/noise ratio of > 60 dB.
Wide temperature operation range of -25...+70°C.
Programming
Selectable DIP-mode for easy configuration of more than 1000 factory calibrated measurement ranges with HART read
only feature.
Selectable HART-mode to enable full HART read-write capabilitytur
Mounting
Units can be mounted side by side, horizontally and vertically, without air gap on a standard DIN rail, even at 70°C ambient
temperature.
Units can be supplied separately (3101 / 3102 / 3331 / 3333 / 3337) or installed on PR 9400 power rail (3111 / 3112 /
3113).
The narrow 6.1 mm housing allows up to 163 units per meter.