EasyManua.ls Logo

PR electronics 3101 - Applications; Technical Characteristics

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 3000V101-UK
TEMPERATURE CONVERTERS
Converts process measurements from Pt100, TC J and K temperature
sensors to voltage or current outputs
Multiple pre-calibrated temperature ranges are selectable via DIP-
switches
High accuracy, better than 0.05% and excellent 50/60 Hz noise
suppression
Fast signal response time < 30 ms
3113 and 3337 with HART® 7 protocol and fast signal response time
< 60 ms
HAR7 protocol enables extended device programming for 3113 and
3337
Slimline 6 mm housing
Applications
• The temperature converters measure standard 2-, 3- or 4-wire Pt100 and/or
TC J & K temperature sensors, and provides an analog voltage or current output.
• High3portisolationprovidessurgesuppressionandprotectsthecontrolsystem
from transients and noise.
• The loop powered devices have high 2-port galvanic separation to eliminate
ground loops.
• ThedevicescanbemountedintheSafeareaorinZone2/Division2areas.
• Approvedformarineapplications.
Technical characteristics
• Highconversionaccuracy,betterthan0.05%ofspan.
• AvisiblegreenLEDindicatesoperationalstatusandstatusoftheinputsensor.
• Allterminalsareprotectedagainstovervoltageandpolarityerror.
• MeetingtheNAMURNE21recommendations,thesystem3000devicesensure
top measurement performance in harsh EMC environments.
• ThedevicesmeettheNAMURNE43standarddefiningoutofrangeandsensor
error output values.
• Highgalvanicisolationof2.5kVAC.
• Excellentsignal/noiseratioof>60dB.