TECHNICIAN SETUP MENU
Tech Setup Steps (Continued from the previous page)
GA
or
EL
GAS
Select GAS for
systems that control
the fan during a call
for heat.
Select ELEC to have
the thermostat
control the fan during
a call for heat.
Fan
Operation
Use the or
key to select 12 or 24
hour clock.
12 Hour Clock
You can select either a
12 or 24 hour clock
setting.
12 or 24
Hour Clock
Use the or
key to turn on or off.
ON
This feature turns your
system on before the
WAKE programming
time to ensure the
enviroment is at the
WAKE setpoint when
the WAKE time period
begins. This recovery
changes over time
based on the previous
days experience.
Morning
Recovery
Use the or
key 5d for 5+1+1,
or 0d for
non-progammable.
5d
You can configure this
thermostat to have a
5+1+1 program or
non-programmable.
Program
Options
Select F for Fahrenheit
temperature read out
or select C for Celsius
read out
ºF for Fahrenheit
ºC for Celsius
ºF
ºF or ºC
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the
swing is reached. For example, if the swing setting is .8 degrees for heating and the thermostat is
set at 70ºF, the first stage will turn on at approximately 69.2ºF. The second stage will turn on at
68.4ºF. The second stage will turn off at 69.2ºF and the first will turn off at 70.8ºF. If third stage is
used, it will turn on at 3x the swing and turn off at approximately 2x the swing.