ELECTRONIC CONTROL PANEL
Page 11 EN - English
PROGRAMMING INSTRUCTIONS -
CONFIGURATION PARAMETERS
Before entering the programming mode, make sure that
the appliance is in the service mode.
All configuration parameters on this appliance have
been pre-programmed in the factory, to offer optimal
performance in a wide range of applications and situations.
Nevertheless it may be necessary or desirable to change any
of these parameters, to further optimize the appliances
performance or to adapt it to the specific requirements of
the installation.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode;
any changes made will NOT be saved!
1. Press the scroll
button and hold it for 6 sec until the
display shows:
2. Within 10 sec, press the up
button; the display will
show:
• Press the up
or down
button to set the units of
measure (Metric or US).
3. Press the scroll
button again on; the display will show:
• Press the up
or down
button to activate the
maintenance reminder function by setting the
maintenance interval, or deactivate the maintenance
reminder function.
4. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the
exchange capacity per litre of resin.
5. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the age
correction factor (%/year) to compensate for capacity
loss of the resin due to aging.
6. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the volume
of resin.
7. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the number
of days between regenerations.
8. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the length
of the regeneration cycle.
• Press the scroll
button again to advance to the next
regeneration cycle.
9. Press the scroll
button again; the display will show:
• Press the up
or down
button to set the
regeneration mode:
Dlyd/Immd: when the remaining capacity equals
the reserve capacity, a delayed regeneration at
the programmed time of regeneration is started;
however when the remaining capacity equals 0
before the programmed time of regeneration is
reached, an immediate regeneration is started.
Immediate: when the remaining capacity equals
0, an immediate regeneration is started.
Note: Delayed manual regeneration is not
available when this regeneration mode is
selected.
Delayed: when the remaining capacity equals the
reserve capacity, a delayed regeneration at the
programmed time of regeneration is started.
10. Press the scroll
button again; the display will show
(only when the regeneration mode is set to ‘Delayed’ or
‘Dlyd/Immd’):
• Press the up
or down
button to set the time of
regeneration.