10. Technical Data
10.1 Electrical specifications
INPUT
Model No. I1000(S) I2000(S) I3000(S)
Phase Single
Frequency (45~55)/(54~66) Hz
Current(A) 9A 17A 26A
OUTPUT
Model No. I1000(S) I2000(S) I3000(S)
Power rating
1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW
Voltage 200/208/220/230/240
×
1
2%
VAC
Frequency
50/60
±
0.2Hz (Battery mode)
Wave form sinusoidal
Derating to 90% when the output voltage is adjusted to 208VAC
Derating to 80% when the output voltage is adjusted to 200VAC
BATTERIES
Model No. I1000 I2000 I3000
Number and type
3
×
12V 7Ah
8
×
12V 7Ah
8
×
12V 7Ah
10.2 Operating Environment
Ambient Temperature 0
o
C to 45
o
C
Operating humidity < 95%
Altitude < 1000m
Storage temperature 0
o
C to 45
o
C