EasyManua.ls Logo

Promation Engineering P2 DC Series - Page 6

Promation Engineering P2 DC Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The Default Settings of the controller are as follows:
• Input Signal: 4-20mA (may be changed)
• Output Signal: 4-20mA (cannot be changed)
• Signal Response: Direct Acting (open = CCW)
• Loss of Command: Fail in Position
Input Signal Options:
• 4-20mA (default)
• 1-5vdc, 0-5vdc, 0-10vdc (Wire as shown on page 4, J2,
terminal 6 and select Command Type from Calibration Menu.
J2 Connector
J1 Connector
Calibration Menu
J3 Connector
for Optional
Feedback
or Modbus
Control
Options
For MODBUS
control paramters,
see
[ProMation Modbus
prmtrs 800-192B.
pdf]
MODE
Button
Select
Button
Select
Button
Fuse
Calibration LED Indicators
Fault Detection:
• Fault Indicator will ash and motor outputs are
turnedo󰀨untilallfaultsarecorrected.
• All Faults show on the same LED
• See Fault Table for priority listing of faults
Controller Notes:
• Limit (Cam) Switches (SW1 and SW2) can cause
a Motor Stall Fault if set too close to the 0° (CW)
or 90° (CCW) positions.
This proportional control card has been calibrated and tested at the factory to operate
between 0 degrees and 90 degrees operating range. Controller position settings control the
actuator, adjustment of cam settings may aff ect controller operation, resulting in a fault.
Proportional Control
Fault LED Indicators
J7 Connector
The AC Controller Shown.
Calibration sequence is the
same for both AC and DC
Diagram of Controller
Page 5 of 17 P2/3 12 24 VDC Proportional Series
FM_P28 24 PN4-DC Ver E 080223

Related product manuals