47
110547-01 - 4/20
FORCEVFO Installation & Service Manual
Table 15-1: Beckett
Boiler Model
Firing
Rate
GPH
Burner
Model
Settings
Nozzle Shipped
Pump
Pressure
Head
(Setting)
Air
Shutter
Air
Band
FORCEVFO-3-075 0.75
AFG
L1
10 2 0.65 X 60B (Hago) Installed
140
FORCEVFO-3-100 1.00 5 2 0.85 x 60B (Hago) Field Provided
FORCEVFO-4-120 1.20
V1(0)
10 0.5 1.00 x 60B (Hago) Installed
FORCEVFO-4-150 1.50 10 6 1.25 x 60B (Hago) Field Provided
FORCEVFO-5-175 1.75 V1(3) 6 6 1.50 x 45B (Hago) Installed
175
FORCEVFO-5-190 1.90 V1(4) 8 4 1.35 x 45B (Hago) Field Provided
15 Burner Specifications