Pulsar Quick Start Manual - Ultra 5
Congratulations on your purchase
of a Pulsar Ultra 5!
This quality system has been developed
with the latest digital ultrasonic tech-
nology for liquids, slurries, and solids.
No more noise and beam angle issues.
It provides non-contacting level, vol-
ume, advanced pump control, differen-
tial level, and open channel flow with 5
user-defined relays. Comes standard
with 110VAC and 24VDC with an iso-
lated 4-20 mA output.
LIQUIDS and SOLIDS
Mount the transducer away from any obstructions, fal-
ling water/solids, rough walls, pumps, switches, etc…
Visualize looking down the echo path of the transducer
and seeing a nice clear shot (2’+ dia.) to the very bot-
tom during fill and empty cycles.
Ensure the maximum level does not come within the
minimum dB blanking distance.
Confirm the inside of the standpipe is smooth and does
not have any protrusions at the weld.
Do not hang the transducer by the cable.
Typically, mount the dB transducer 1/2 the tank radius.
(Call Pulsar Technical Support for Special Service
Passcode and Instructions 850-609-1777.)
LIQUIDS
Dome top tanks will require Gain & Algorithm change.
If reading false level, use P21 and set true distance
SOLIDS
Consult factory if the silo is extremely dusty—we can
increase the return signal strength (even during fill).
DATEM may map-out the true echo. Use P21 to set
true distance and turn “Update Datem” off!
If acoustically noisy, change Algorithm to Largest.
TRANSDUCER WIRING
TERMINAL IF SPLICING (shielded pair)
RED = POWER RED = BLACK
WHITE = SIGNAL WHITE = WHITE
BLACK & GREEN = 0V BLACK & GREEN = SHIELD
Use any standard, 2 conductor/shielded pair for splic-
ing (recommend 18 AWG gauge, UV protected)
Use 16 AWG gauge if going 500 - 3,000 ft cable run.
Transducer shield is required - do not cut or float!
Battery is actually the 24VDC terminals.
If I.S. Zone 0 is required, consult factory for details.
Above wiring diagram is on the back of terminal cover.
0-8 ft .5-10 ft 1-20 ft 1-33 ft 1.7-50 ft 2-82 ft 3-132 ft
Mach3 dB 3 dB 6 dB 10 dB 15 dB 25 dB 40 Aiming Kit
Pulsar, Inc., PO Box 799, Shalimar, FL 32579 Phone: (850) 609-1777 Fax: (850) 651-4777 support@pulsar-us.com
Press to close enclosure!
TRANSDUCER INSTALLATION TROUBLESHOOTING