    turnermichaelJul 27, 2025
    What to do if my Pulsar Controller displays an incorrect reading for the current level?
    • H
      Hannah RamosJul 27, 2025
      If the Pulsar Controller displays an incorrect reading, measure the actual distance from the transducer head to the surface of the material. Then, enter Program Mode and directly access P21 (Set Distance). Type in the measured distance, press ENTER, and then ENTER again when prompted. Wait until SET is displayed and return to Run Mode. The display should now update to the correct reading.
  • S
    Shelly HolmesJul 31, 2025
    Why do the LEDs change color, but the relays don't change state on my Pulsar ULTRA 5?
    • S
      sherry68Jul 31, 2025
      If the LEDs on your Pulsar Controller change color at the relevant relay switch points, but the relays do not change state, check the power supply to the unit and ensure the voltage selector is set to the correct position.
  • J
    jacobhunterAug 6, 2025
    What to do if material level is consistently incorrect by the same amount on my Pulsar ULTRA 5?
    • S
      Samuel FlynnAug 6, 2025
      If the material level displayed on your Pulsar Controller is consistently incorrect by the same amount, check the empty level (P105), display offset (P802), and measurement offset (P851).
  • L
    Larry TorresAug 11, 2025
    What to do if my Pulsar ULTRA 5 Controller displays 'No Xducer'?
    • J
      janet93Aug 11, 2025
      If your Pulsar Controller displays 'No Xducer', check the wiring to the transducer.
  • J
    Johnny HarrisAug 16, 2025
    How to fix a Pulsar ULTRA 5 that displays 'Xducer Flt'?
    • A
      Ashlee CunninghamAug 16, 2025
      If your Pulsar Controller displays 'Xducer Flt' because of a fault with the transducer wiring, check the wiring to the transducer.
  • P
    Patrick TateAug 21, 2025
    How to troubleshoot a blank display and non-firing transducer on a Pulsar Controller?
    • R
      Ryan FitzgeraldAug 21, 2025
      If the display is blank and the transducer is not firing on your Pulsar Controller, check the power supply, voltage selector switch, and fuse.