Page 201
P804 Display Conversion
The reading is multiplied by the value of this parameter before being
displayed. The default is 1.0, but if for example you wanted to display the
reading in yards, then set the Measurement Units (P104) to feet, and set
P804 to 3.
P805 Display Source
When Ultra Wizard = 1 Level/Volume or 2 Pump/Differential
This parameter determines which input the display will relate to, it is
automatically set to the correct option when selecting the Mode P100, and
Xducer P101, under normal circumstances it will not require changing.
Option
Description
0 = Default (Default)
Displays reading obtained from selected
Mode (P100).
1 = Aux (Optional)
Displays level from optional Aux. Input.
2 = Xducer 1
Displays level from Xducer 1
3 = Xducer 2
Displays level from Xducer 2.
Failsafe
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display, relays and the
mA output are held at their last known values until a valid reading is
obtained.
If required, then you can change this so that the unit goes to high (100% of
span), or low (empty) as follows:
Option
Description
1 = Known (Default)
Remain at the last known value
2 = High
Will fail to the high value (100% of Span).
3= Low
Will fail to the low value (empty)
See Also P218, P228, P238, P248, P258 - Relay Fail-safe and P840 mA Output Fail-safe

Table of Contents

Other manuals for Pulsar ULTRA 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar ULTRA 5 and is the answer not in the manual?

Pulsar ULTRA 5 Specifications

General IconGeneral
BrandPulsar
ModelULTRA 5
CategoryController
LanguageEnglish

Related product manuals